A Spectrally Interrogated Polarimetric Optical Fiber Sensor for Current Measurement with Temperature Correction

1
Photonics Research Center, Université du Québec en Outaouais, Rue 101 St-Jean Bosco, Gatineau, QC J8X 3G5, Canada
2
Central Laboratory of Applied Physics, Bulgarian Academy of Sciences, 61 Sanct Peterburg Blvd., 4000 Plovdiv, Bulgaria
3
Institute of Optical Materials and Technologies “Acad. J. Malinowski” (IOMT), Bulgarian Academy of Sciences (BAS), 109 “Acad. G. Bonchev” Str., 1113 Sofia, Bulgaria
4
Photonics Laboratory, Department of Mathematics, Physics and Information Technologies, Faculty of Economics, University of Food Technologies, 26 Maritsa Blvd., 4000 Plovdiv, Bulgaria
*
Author to whom correspondence should be addressed.
Sensors 2023, 23(23), 9306; https://doi.org/10.3390/s23239306
Submission received: 11 October 2023 / Revised: 14 November 2023 / Accepted: 15 November 2023 / Published: 21 November 2023
(This article belongs to the Special Issue Integrated and Optical Fiber Magnetic and Electric Field Sensors)

Abstract

:
We report on a study of the temperature dependence of the response of a BSO crystal based polarimetric current sensor with spectral interrogation. Two possible interrogation schemes are discussed. The spectral dependence of the optical rotation along the crystal caused by temperature and current changes is investigated, and approximate dependences for the sensitivities to current SI and temperature ST are derived. A mixed term in the response with spectral interrogation is revealed, the elimination of which is achieved by tracking wavelength shifts Δλ1 and Δλ2 of two distinct extrema in the polarimetric response. A temperature independent second degree equation for the current changes ΔI as a function of the measured spectral shifts is derived and tested.

1. Introduction

Electric current and/or magnetic field fiber optic sensors have been known, developed and commercialized [1] for quite some time for the purposes of the power industry [2] and special applications [3]. These sensors are based either on the Faraday effect in the fiber itself, or in bulk materials [4] which use optical fiber transducers, such as fiber Bragg gratings (FBG), interferometers, or refractometers [5,6,7,8,9,10,11] in combination with magnetic field sensitive materials. These sensors are characterized by specific advantages and disadvantages as well as varying simplicity and complexity.
Among the simplest and most straightforward solutions are the polarimetric sensors using magneto-optical materials such as BSO (Bi12SiO20) and BGO (Bi4Ge3O12) crystals because of their high Verdet constant and because their wavelength dependence has been accurately measured and is well known [12,13]. The first polarimetric fiber optic sensor using BSO/BGO crystals [14,15], however, operated at a single wavelength and detected amplitude changes of the polarimetric response. These crystals are also temperature dependent [16,17], which limits the performance of the sensor. To account for temperature dependence, detection at two wavelengths has been proposed [18], or the temperature dependence of the BGO crystal has been taken into account [19]. The problem of the temperature dependence for the other types of current sensor has been addressed in different ways depending on the interrogation scheme and the magneto-sensitive material, using either temperature compensation [18,19,20,21,22,23] or simultaneous magnetic field and temperature measurement in the case of magnetic field sensors with spectral interrogation [24,25,26,27,28,29].
We have recently shown [30,31] that the well-known fluorescence in BSO crystals [32] can be used to generate a broad spectrum under ultraviolet or white LED excitation, which serves as a broadband source for a polarimetric scheme with spectral interrogation. We have also reported [33] that the BSO crystal based polarimetric sensor exhibits a wavelength dependent temperature response.
In the present work, we measure the optical activity of a BSO crystal at different temperatures, currents, and wavelengths and establish the spectral and temperature dependence of the intrinsic and the magnetic field induced polarization rotation. We show that, using a white LED, the spectrally interrogated polarimetric fiber optic current sensor can be used to eliminate the temperature dependence in the measurement of the electric current.
Section 2 presents the general experimental setup, the principle of operation, and the two possible interrogation techniques. Section 3 is devoted to the measurement of the spectral dependence of temperature-influenced optical activity from which we derive the spectral, temperature, and current dependences of the sensitivities to current and to temperature. To eliminate the temperature dependence, we use the spectral shifts of two extrema of the polarimetric spectral response and derive an expression for the current changes. The performance of the current sensor is simulated numerically.

2. Principle of Operation and Experimental Arrangement

2.1. Experimental Setup

The experimental setup in Figure 1a was used to generate a broad spectrum from 520 nm to 800 nm in the BSO crystal and to observe the spectral distribution of the polarimetric responses. The side view with the crystal size are shown in Figure 1b, while Figure 1c shows the side glow caused by fluorescence and scattering from the crystal with white LED excitation, whose built-in blue LED is the major cause of fluorescence in the crystal. Figure 1d shows the front view of the fluorescent light coming out from the crystal when illuminated via a 1 mm diameter optical fiber with LEDs at 385 nm and 440 nm. A low cost film polarizer LPVISE2 × 2 (Thorlabs, Newton, NJ, USA) with extinction ratios of >100:1 for 400–740 nm, >1000:1 for 500–700 nm, and >5000:1 for 530–690 nm ranges was used in the experiments. The polarimetric response of the broadband spectrum is given by the expression [31]:
I = 1 4 { 1 + cos [ 2 ( ϕ + θ α ) ] }
In (1) θ and α are the polarizer and analyzer orientations and
ϕ = Δ β L
is the accumulated phase along the circularly birefringent BSO crystal whose length is L, and Δβ = βLβR is the propagation constant difference between the left and the right circularly polarized waves along the crystal. This difference is both wavelength and temperature dependent, and is expressed as [31]:
Δ β ( λ , T ) = ρ ( λ , T ) + V B ( λ , T ) B
In (3) ρ (deg/mm) is the optical rotatory power of the crystal and the additional rotatory power ρF = VBB caused by the Faraday effect, B is the magnetic field and VB is the Verdet constant. The wavelength dependences of ρ(λ) and VB(λ) are well known [12,13], both decrease with wavelength and VB is proportional to ρ [17]. However, the temperature dependences have been insufficiently studied and later in the paper we present more detailed results on them. Inserting (3) and (2) into (1), we have, for the wavelength and temperature dependent intensity I(λ, T) [30,31]:
I ( λ , T ) = 1 4 { 1 + cos [ Φ ( B , T , λ ) ] } = 1 4 { 1 + cos [ 2 ( ρ ( λ , T ) + V B ( λ , T ) B ) L + 2 ( θ α ) ] }
with Φ(B, T, λ) being the total phase in the polarimetric response. The typical spectral responses of a polarimetric sensor to changes of the polarizer/analyzer orientations and to current (magnetic field) are shown in Figure 2. The plots show that the particular position of the modulated pattern can be fine-tuned by changing the orientation of the analyzer/polarizer via the θα term. The changes of the measurand (current/magnetic field) and of the temperature lead to shifts of the polarimetric response, as shown in Figure 2b.

2.2. Principle of Operation and Sensitivities

Unlike the single wavelength polarimetric scheme [14] in which the intensity (4) is measured, in our arrangement, we observe by a spectrometer the whole spectrum, which exhibits an oscillatory response. Since both ρ(λ) and VB(λ) decrease with wavelength, the period of the wavelength dependent response Λ (which is the free spectral range–FSR) increases with wavelength. As the angle between polarizer and analyzer can be varied, we can tune the phase 2(θα) and thus fix the position of the polarimetric response.

2.3. Interrogation Detection Techniques

There are two detection techniques that can be used to detect the changes in the polarimetric spectral response. In the first we track the wavelength position of a minimum λm or a maximum λM, as the magnetic field/electric current changes. Thus, the wavelength shifts δλM = δλM − δλM,0 of a maximum and δλm = δλm − δλm,0 of a minimum, defined with respect to some wavelength positions at I = 0 A and T = T0, are tracked. In the second, we observe the intensities that are +π/2 and –π/2 phase-shifted with respect to an extremum, namely IM+ and IM for a maximum or Im+ and Im for a minimum, and calculate the differences and the sums of intensities that are π-shifts with respect to one another: ΔM = IM+IM, ΣM = IM+ + IM and Δm = Im+Im, Σm = Im+ + Im and then calculate the normalized differences NM = ΔMM and Nm = Δmm which change with current/magnetic field and with temperature.

2.3.1. Extrema Wavelength Shifts

In this case, for a given magnetic field B (or current I) and temperature T, the wavelengths λM,k and λm,k of the k-th maximum and minimum of the polarimetric response are those for which the phase Φ from (4) is:
Φ M ( B , T , λ M , k ) = 2 k π   max   and   Φ m ( B , T , λ m , k ) = ( 2 k + 1 ) π   min
and the phase change ΔΦ is then
Δ Φ k = Φ k λ Δ λ k + Φ k I Δ I + Φ k T Δ T
As mentioned in [30,31], the periodic response is caused by the spectral dependence of the optical activity ρ(λ) and the Verdet constant VB(λ). When we track the shifts Δλk of an extremum (at λM,k or λm,k) with respect to the position for I = 0 (B = 0) caused by changes of the magnetic field (or current) ΔB (or ΔI) and of the temperature ΔT, the resultant phase change ΔΦ of the phases ΦM or Φm is zero because the condition (5a) for the tracked extremum remains constant i.e., ΦM = 2kπ = const and ΦM = 2kπ = const. The expression (5b) becomes null, and solving with respect to Δλ we obtain:
Δ λ k = λ k λ k , 0 = ( Φ B / Φ λ ) Δ B ( Φ T / Φ λ ) Δ T = S B Δ B + S T Δ T
where SB and ST are the sensitivities to magnetic field and temperature changes:
S B = Δ λ k Δ B ,   S T = Δ λ k Δ T
In (5a,b) and (6a,b) the instantly tracked λk is either λM,k or λm,k and Δλ k is the wavelength shift of the extremum from the initial value λk,0 for which I = 0 and T = T0. This type of interrogation is illustrated in Figure 3a. Both the magnitude and the sign of the current/magnetic field can thus be measured. Figure 4a shows the wavelength shifts of the extrema from the response in Figure 3a, which prove to be linear with wavelength, while Figure 4b shows the correspondingly measured sensitivities which increase with wavelength [30,31] because they are inversely proportional to dispersion of the optical activity and the Verdet constant.

2.3.2. π-Shifted Normalized Differential Response

In this case, the intensities I k ¨ + and I k ¨ of the polarimetric response around the k-th extremum ( I M , k ¨ ± and I m , k ¨ ± ) that are π-shifted to each other can be defined as:
I k ¨ + = I 0 cos [ 2 φ k + 2 ( θ α ) + π 2 ] I k ¨ = I 0 cos [ 2 φ k + 2 ( θ α ) π 2 ]
The normalized differential responses around the k-th maximum or the minimum are defined as:
N M , k = I M , k ¨ + I M , k ¨ I M , k ¨ + + I M , k ¨ ,   N m , k = I m , k ¨ + I m , k ¨ I m , k ¨ + + I m , k ¨
In the initial state I M , k ¨ + = I m , k ¨ , but when the polarimetric response shifts to the right the difference Δ = I M , k ¨ + I M , k ¨ becomes positive and vice versa, as illustrated in Figure 3b by the red and blue vertical arrows. Therefore, both the amplitude and the sign of the current/magnetic field can be detected. The sensitivities to magnetic field/current and to temperature are defined in this case as:
Π B , k = 100 Δ N k Δ B   or   Π I , k = 100 Δ N k Δ I ,   Π T , k = 100 Δ N k Δ T
Figure 5 presents the responses of the normalized differential signals according to the π-shifted interrogation technique. As is seen, the responses have different sensitivities, though not quite as linear as those from Figure 4. The sensitivity in this case shows similar wavelength dependence as with the first interrogation method (Figure 4b).

2.3.3. Comparison

In the present paper we present a more detailed analysis of a current sensor with temperature correction using the first scheme; however, some general comparisons between the two interrogation schemes can be outlined as follows:
(i)
The responses of the π-shifted method exhibit nonlinearities compared with the extrema shift method;
(ii)
The normalized differential signal is faster to calculate compared with the extrema shift method and is more appropriate if fast changing short circuit current changes are to be detected, in which case slowly varying temperature induced noise is irrelevant;
(iii)
The resolution of the π-shifted method is better because the signals are away from minima and less sensitive to noise.

3. Experiment and Results

3.1. Experimental Setup

To study the possibility for temperature corrected current measurements, we need to know the dependences of the optical activity and the Verdet constant on the wavelength ρ(λ), V(λ) and on temperature ρ(T), V(T). The experimental setup used to obtain the needed measurements is shown in Figure 6.
The light source was a white halogen lamp (Ocean Optics) and the spectrometer was an Avantes VASPEC-ULS2048CL-EVO, (0.5 nm resolution and a 400 nm to 900 nm range). The light from the source was coupled to a 600 μm large core quartz-polymer lead-in fiber, collimated at its output, polarized by a polarizer through an angle θ, traversing the BSO crystal, passed through an analyzer oriented to an angle α, and focused to the same type of a lead-out fiber. Alternatively, for current and temperature measurements, the white light halogen lamp was replaced by a white LED. The BSO crystal (4 × 4 × 25) was placed in an aluminum holder and was heated/cooled using a thermoelectroc cooler (TEC). The polarizer was fixed with the transmission axis along the horizontal axis of the crystal. Only the analyzer was rotated during measurements of the optical activity and its temperature dependence. The temperature could be varied from −32 °C to 62 °C. The power supply could provide a current in the range from −30 A to +30 A (±0.1 A) which fed the solenoid coil to create a homogeneous magnetic field along the BSO crystal, as shown in Figure 6.

3.2. Results of Optical Activity Measurements

Using the setup shown in Figure 6, we performed a sequence of measurements in which we changed the temperature T and current I across the solenoid and measured the output angle of rotation of the polarization at a particular wavelength λ. The measurements were made by compensation of the polarization rotation via turning the analyzer angle φ so that a given minimum at a specified wavelength in the polarimetric response (Figure 2) remained at the same position, which meant that for a given minimum (k = constant) as
Φ k = 2 [ ρ ( λ k , T ) + V I ( λ k , T ) I ] L + 2 ( θ φ ) = ( 2 k + 1 ) π
The sequence of measurements was as follows:
(i)
A wavelength from among the following 540 nm, 570 nm, 600 nm, 630 nm, 660 nm and 690 nm was chosen, starting from the highest value. In the absence of magnetic field (I = 0 A) and at room temperature (≈22 °C) the analyzer was rotated until a minimum of the response coincided with the chosen wavelength of measurement (690 nm for example);
(ii)
For a chosen value of the wavelength λk, a value of the current as fixed between I = −30 A and I = 30 A. For a fixed value of the current, the temperature was varied between T = −30 °C and 60 °C, and for each temperature the analyzer was rotated to compensate for the temperature and current induced phase changes (26a,b) due to the ρk,T), VIk,T) and I, and the particular value for φ was found;
(iii)
After the temperature was scanned, a new value for the current for the same wavelength was set and then the temperature scanning was repeated;
(iv)
After all currents were scanned, the next wavelength was chosen and the procedure from (i) to (iii) was repeated.
The results obtained provided the possibility for the following analysis to be performed.
First, the only spectral and temperature dependence was in the optical activity and the Verdet constant, and second, neither of them depended on the current, so the compensation angle can be represented as.
φ ( λ , I , T ) = V I ( λ , T ) L . I + ρ ( λ , T ) L   with   V I ( λ , T ) I = V ( λ , T ) B
Second, we analyzed the results for I = 0, which revealed the dependences ρk, T), so we have
φ 0 ( λ , T ) = φ ( λ , 0 , T ) = ρ ( λ , T ) L
Figure 5a shows a plot of the rotation angle caused by optical activity vs. temperature for the above six wavelengths in the absence of a magnetic field (I = 0). As is seen from this figure, the optical rotation linearly reduces with temperature and can be represented in the form:
φ 0 ( λ , T ) = ρ ( λ , T ) L = a ρ ( λ ) T + ρ 0 ( λ ) L
where the thermal coefficient aρ(λ) that determines the slope of the lines in Figure 7a as well as the optical activity ρ0 are wavelength dependent.
Third, from the measurements at different temperatures in the −30 °C to 60 °C range for different currents from −25 A to +25 A, we can retrieve the optical rotation VI.L (deg/A) due to the magneto-optic effect and its wavelength dependence presented in Figure 8. In that figure we plot VI(λ). L for three temperatures, −30 °C, 0 °C, and 60 °C, and it is seen that the temperature deviations vary randomly in either direction. The relative error due to temperature-dependent deviations of the magneto-optic activity varied with wavelength, and, on average, was found to be ≈0.7%.
We thus conclude that
V I ( λ , T ) = V ( λ ) + ε ( T ) V ( λ )
where ε(T) is a negligible thermally dependent correction.

3.3. Approximations

The experimental plots obtained for ρ0(λ), aρ(λ) and V(λ) are found to be sufficiently well approximated by power law functions, namely as:
ρ 0 ( λ ) = R 0 λ r   R 0 = 4   ×   10 8 ,   r = 2.573   ( R 2 = 0.9995 )
a ρ ( λ ) = A 0 λ a   A 0 = 60704 ,   a = 2.511   ( R 2 = 0.9878 )
V I ( λ ) = V 0 λ v   V 0 = 760533 ,   v = 2.728   ( R 2 = 0.9896 )
Based on the above we can write (14) as
φ ( λ , I , T ) = ρ ( λ , T ) L + V I ( λ ) L . I = a ρ ( λ ) T . L + ρ 0 ( λ ) . L + V I ( λ ) I . L
and for λ from 540 nm to 700 nm and T from −30 °C to +60 °C, the power law approximations (21) can be used for all wavelength dependences:
φ ( λ , I , T ) = A 0 λ a T + R 0 λ r + V 0 λ v . I . L

4. Simultaneous Current and Temperature Measurement Technique

4.1. Sensitivities to Current and Temperature

To realize temperature corrected current measurement the non-linear power-law approximations for aρ(λ), ρ0(λ) and V(λ) are simplified according to the following procedure:
(i)
Use the power law approximations (21) to study the responses to current and temperature changes and determine the sensitivities SI and ST;
(ii)
Study the wavelength, temperature, and current (magnetic field) dependences of SI and ST;
(iii)
Develop a method for simultaneous two-parameter measurement.
We first model the white light LED spectral distribution used in the sensor by a shifted Gamma function defined as [31]:
S ( λ ) = β α Γ ( α ) ( λ λ 0 ) α e β ( λ λ 0 )
Taking into account (21) and (22a,b), the intensity distribution at the analyzer can be represented as
I ( λ , I , T ) = I 0 4 S ( λ ) { 1 + cos [ ( A 0 λ a T + R 0 λ r + V 0 λ v . I ) L + 2 ( θ φ ) ] }
The parameters for the Gamma function are as follows: λ0 = 515 nm, α = 3.75 and β = 27. The theoretical fit using (17) a real polarimetric response at analyzer angle 0° is presented in Figure 7 and is compared with the response at 60°.
The full differential of the phase per unit length dΦ/2L is found from (3b)
d Φ 2 L = ( a A 0 λ a 1 T r R 0 λ r 1 v V 0 λ v 1 . I ) d λ + ( v V 0 λ v 1 ) d I + ( A 0 λ a ) d T
d Φ 2 L = F λ d λ + F I d I + F T d T
In case of spectral interrogation by extremum tracking, dΦ = 0, and for δλ we find:
d λ = F I F γ d I F T F λ d T = S I d I + S T d T
S I = d λ d I = F I F γ ,   S T = d λ d T = F T F γ
As the power law expressions are non-linear, we proceed to the second step outlined above and perform a study of the wavelength, temperature, and current (magnetic field) dependences of SI(λ, I, T) and ST(λ, I, T). To do that, we change the current I at a constant temperature T, and then change temperature for constant current and measure the resulting wavelength shifts of the minima and maxima in the distribution from Figure 9. Then, we plot the dependence of Δλ vs. I for different temperatures for each extremum, as well as Δλ vs. T for different currents, from which we determine the needed sensitivities.
Δ λ = S I ( λ , T ) Δ I + S T ( λ , I ) Δ T
Figure 10 shows the wavelength changes of four minima. The wavelength dependence for the current sensitivity SI(λ) is experimentally confirmed in ref. [31], and, as we see at each wavelength, the Δλ(I) dependence is linear. So is the SI(λ) over the range of wavelengths above 550 nm, though weakly dependent on temperature. As is seen from Figure 10b, the sensitivity to current is linearly dependent on the wavelength and can be represented as follows:
S I ( λ ) = A 0 ( T ) + A 1 ( T ) λ   ( n m / A )
The linear fits of each of the coefficients presented in Figure 10c,d below can be represented as follows:
A 0 ( T ) = A 00 + A 01 T   ( nm / A )   and   A 1 ( T ) = A 10 + A 11 T   ( 1 / A )
The wavelength shifts of the four minima with temperature and the temperature sensitivity on the wavelength ST(λ) at different current levels are presented in Figure 11.
From Figure 9b it is seen that the temperature sensitivity ST,I) is linearly dependent on the wavelength and can be written as:
S T ( λ , I ) = B 0 ( I ) + B 1 ( I ) λ   ( n m / ° C )
where B0(I) and B1(I) are also linear functions of the current Figure 9c,d and are written as:
B 0 ( I ) = B 00 + B 01 I   ( nm / ° C )   and   B 1 ( T ) = B 10 + B 11 I   ( 1 / ° C )
As follows from (21)
λ λ 0 = S I ( λ , T ) ( I I 0 ) + S T ( λ , I ) ( T T 0 )

4.2. Two Points Method for Simultaneous Two-Parameter Measurement

In this form, the unknown quantities are the current I and temperature T and after insertion of (22b) into (22a) and of (23b) into (23a) and, after some rework for the k-th extremum tracked, we obtain
λ k λ k 0 = Δ λ k = A k Δ I + B k Δ T + C k Δ I Δ T
where
A k = A 00 + A 10 λ k A k T 0   A k = A 01 + A 11 λ k
B k = B 00 + B 10 λ k B k I 0   B k = B 01 + B 11 λ k
C k = A k + B k
Equation (24) contains a mixed term proportional to ΔIΔT. To eliminate the temperature dependence, we chose two extrema wavelengths λ1 and λ2 (k = 1, 2) to track to our choice. By varying the orientation of the analyzer we can fine tune the position of the pattern. Equation (24) then is written for each of the wavelengths as:
Δ λ 1 = A 1 Δ I + B 1 Δ T + C 1 Δ I Δ T
Δ λ 2 = A 2 Δ I + B 2 Δ T + C 2 Δ I Δ T
Solving (26a,b) with respect to the mixed ΔT term and eliminating the temperature dependence leads to a quadratic equation with respect to the current:
a Δ I 2 + b Δ I + c = 0
where
a = A 1 C 2 C 1 A 2 ,   b = Δ λ 2 C 1 Δ λ 1 C 2 + A 1 B 2 B 1 A 2 ,   c = Δ λ 2 B 1 Δ λ 1 B 2
Solving (27) with respect to ΔI yields
Δ I = b b 2 4 a c 2 a
The electric current measurement procedure runs thus as follows:
(i)
The coefficients from Table 1 are substituted into (25a–c);
(ii)
By fixing the position of the analyzer with respect to the polarizer, a desirable position of the spectral response is fixed for I0 = 0 and T = T0 which quantities are also to be inserted into (25a–c). The two extrema whose shifts are to be monitored are fixed, and under these conditions their values λ10 and λ20 are measured and substituted into (25a–c) as well;
(iii)
The instant values of the extrema λ1 and λ2 are measured over regular intervals t and are inserted into (25a–c) and into (28) for the coefficients a, b, and c from (27);
(iv)
The current change is calculated (29).
To test the method, we perform the above procedure by setting in (29) the current I from −100 A to +100 A for temperatures T = −30 °C, 0 °C, 30 °C, 60 °C, and 90 °C which causes the spectral response to shift. For each combination of current and temperature we determine the values of the wavelengths λ1, λ2, and λ3 of the three observable minima, which values are inserted into (25a–c). The reference wavelength values λ1,0 = 525.7 nm, λ2,0 = 572.8 nm, and λ3,0 = 639.7 nm from (24) are at T0 = 0 and I0 = 0. The pairs of wavelengths to determine the current are (λ1, λ3) and (λ2, λ3). Figure 9 shows the correspondence between the preset value of the current I and the calculated Ic for each of the pairs from Equation (29).
The results obtained for the temperatures from −30 °C to +90 °C reveal that the correspondence is linear and close to an identity function, yet from the linear fits, the proportionality coefficient is 0.9438 for the first pair and 0.9316 for the second (Figure 12a,b). We first note that, on average, the responses are the same for all temperatures. Second, a certain non-linearity is observed, and third, the two correspondences are differently offset from the origin of the coordinate system. Figure 13a shows the correspondences averaged over all temperatures with a third-order polynomial. Figure 13b shows the average of the two responses from Figure 13a. The first and third order polynomials are summarized in Table 2. Figure 12 and Figure 13 reveal that the slight non-linearity is observed at the extremities for negative currents. These we assume are due to the neglect of the weak temperature dependence of the Verdet constant from Figure 8b and to extending by a factor of more than three the current range in the simulations compared with the range of measurements to determine the sensitivities. The high values of the coefficient of determination R2 for the third-order polynomial mean that a convenient look-up table can be compiled to list the correct value of the preset current.
Having presented the principle of temperature correction using wavelength shifts at two different wavelengths, we can summarize the advantages of spectral interrogation as follows:
First, since sensitivities to current and temperature vary with wavelength, by measuring the responses at two different wavelengths it is possible to eliminate the temperature dependence.
Second, the normalized differential π-shifted response and the signals measured to track the spectral shifts do not depend on the power level of the source and are immune to power fluctuations.
Third, the optical scheme with a broadband source and spectral interrogation is simpler that those at two wavelengths with temperature compensation which require polarization beamsplitters, fiber optic splitters [18], or those based on magnetostrictive materials and magnetic fluids [20,21,22,23,24,25,26,27,28,29].

5. Conclusions

The performed measurements, subsequent analysis, and simulations of a polarimetric current sensor with spectral interrogation allow us to draw the following conclusions:
  • Two types of spectral interrogation technique could be used: Wavelength shifts of the minima and/or maxima and normalized differential intensity response at pairs of wavelengths which are π-shifted over the spectral range. In both cases the sensitivities to current are wavelength dependent;
  • We performed detailed measurements on the temperature, current, and spectral dependences of the intrinsic and magnetic field induced optical activity of BSO crystals in the range from 540 nm to 690 nm, current range from −30 to +30 A, and temperature range from −30 °C to 60 °C;
  • The temperature dependence of the intrinsic optical activity ρ(λ,T) was found to be linear in the form ρ(λ,T) = ρ0(λ) + a(λ)T within the above range, while the wavelength dependence of the coefficients ρ0(λ) and aρ(λ) could be fitted with coefficients of determination of R2 = 0.9878 or better;
  • The temperature dependence of the Verdet constant was found to be very weak, and over a ΔT = 90 °C temperature range is less than 1.08 × 10−3 deg/A/mm, typically <7.2 × 10−4 deg/A/mm above 570 nm. The wavelength dependence of the Verdet constant could be fitted by a power law with R2 = 0.989;
  • On the basis of the above established approximations, it was found that the wavelength shift of an extremum is a linear combination of the current and temperature changes, but contains a mixed term. By making use of spectral shifts at two extrema λ1 and λ2, the temperature dependence was lifted and a third-order polynomial equation for current changes ΔI was derived;
  • A straightforward current measurement procedure was proposed and tested numerically.

Author Contributions

T.E.—conceptualization, investigation, formal analysis, writing of the manuscript, funding, G.D.—conceptualization, methodology, investigation, supervision, funding, P.K.—data curation, investigation, resources, V.V.—investigation, resources. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Bulgarian National Science Fund, grant number KP-06-N48/2 entitled “Spectral polarimetry of polarized fluorescence in magneto-optical materials and its application to precision magnetic field sensors”.

Data Availability Statement

Data are contained within the article.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Zhang, J.; Wang, C.; Chen, Y.; Xiang, Y.; Huang, T.; Shum, P.P.; Wu, Z. Fiber structures and material science in optical fiber magnetic field sensors. Front. Optoelectron. 2022, 15, 34. [Google Scholar] [CrossRef]
  2. Bohnert, K.; Gabus, P.; Kostovic, J.; Brändle, H. Optical fiber sensors for the electric power industry. Opt. Lasers Eng. 2005, 43, 511–526. [Google Scholar] [CrossRef]
  3. Leysen, W.; Gusarov, A.; Wuilpart, M.; Beaumont, P.; Boboc, A.; Croft, D.; Bekris, N.; Batistoni, P. Plasma current measurement at JET using polarimetry-based fibre optic current sensor. Fusion Eng. Des. 2020, 160, 111754. [Google Scholar] [CrossRef]
  4. Mihailovic, P.; Petricevic, S. Fiber Optic Sensors Based on the Faraday Effect. Sensors 2021, 21, 6564. [Google Scholar] [CrossRef]
  5. Liu, C.; Shen, T.; Wu, H.-B.; Feng, Y.; Chen, J.-J. Applications of magneto-strictive, magneto-optical, magnetic fluid materials in optical fiber current sensors and optical fiber magnetic field sensors: A review. Opt. Fiber Technol. 2021, 65, 102634. [Google Scholar] [CrossRef]
  6. Peng, J.; Zhang, S.; Jia, S.; Kang, X.; Yu, H.; Yang, S.; Wang, S.; Yang, Y. A highly sensitive magnetic field sensor based on FBG and magnetostrictive composite with oriented magnetic domains. Measurement 2022, 189, 110667. [Google Scholar] [CrossRef]
  7. Zhang, H.; Xie, Z.; Yan, H.; Li, P.; Wang, P.; Han, D. High sensitivity and large measurement range magnetic field micro-nano fiber sensor based on Mach-Zehnder interference. Opt. Laser Technol. 2022, 156, 108455. [Google Scholar] [CrossRef]
  8. Shuhao, C.; Sergeev, M.; Petrov, A.; Varzhel, S.; Sheng, C.; Li, L. Highly sensitive vector magnetic field sensors based on fiber Mach–Zehnder interferometers. Opt. Commun. 2022, 524, 128725. [Google Scholar] [CrossRef]
  9. Wang, X.; Zhao, Y.; Lv, R.; Zheng, H. Optic-fiber vector magnetic field sensor utilizing magneto-shape effect of magnetic fluid. Measurement 2022, 202, 111829. [Google Scholar] [CrossRef]
  10. Alberto, N.; Domingues, M.F.; Marques, C.; André, P.; Antunes, P. Optical Fiber Magnetic Field Sensors Based on Magnetic Fluid: A Review. Sensors 2018, 18, 4325. [Google Scholar] [CrossRef]
  11. Li, X.; Yu, Q.; Zhou, X.; Zhang, Y.; Lv, R.; Zhao, Y. Magnetic sensing technology of fiber optic interferometer based on magnetic fluid: A review. Measurement 2023, 216, 112929. [Google Scholar] [CrossRef]
  12. Tassev, V.; Gospodinov, M.; Veleva, M. Optical activity of BSO crystals doped with Cr, Mn and Cu. Opt. Mater. 1999, 13, 249–253. [Google Scholar] [CrossRef]
  13. Tassev, V.; Diankov, G.; Gospodinov, M. Measurement of optical activity and Faraday effect in pure and doped sillenite crystals. Proc. SPIE 1996, 2529, 223–230. [Google Scholar]
  14. Diankov, G.L.; Tassev, V.L.; Gospodinov, M. Fiber optic magnetic field sensor head based on BSO crystal. Proc. SPIE 1996, 3052, 390–393. [Google Scholar]
  15. Wang, L.; Huang, Y.; Deng, C.; Hu, C.; Wang, T. A Compact Polarimetric Fiber-optic Sensor Based on Bi4Ge3O12 Crystal for Ultra-high Surge Current Sensing. In Proceedings of the 26th International Conference on Optical Fiber Sensors, Lausanne, Switzerland, 24–28 September 2018; ISBN 978-1-943580-50-7. [Google Scholar]
  16. Isik, M.; Delice, S.; Gasanly, N.M.; Darvishov, N.H.; Bagiev, V.E. Temperature-dependent band gap characteristics of Bi12SiO20 single crystals. J. Appl. Phys. 2019, 126, 245703. [Google Scholar] [CrossRef]
  17. Mihailovic, P.; Petricevic, S.; Stankovic, S.; Radunovic, J. Temperature dependence of the Bi12GeO20 optical activity. Opt. Mater. 2008, 30, 1079–1082. [Google Scholar] [CrossRef]
  18. Lessmann, F.; Jenau, F. Temperature Compensation Method for an Optical Direct Current Sensor Using Two Wavelengths and Technical Current Ripple. In Proceedings of the 2018 IEEE International Conference on Environment and Electrical Engineering and 2018 IEEE Industrial and Commercial Power Systems Europe (EEEIC/I&CPS Europe), Palermo, Italy, 12–15 June 2018; pp. 1–4. [Google Scholar]
  19. Mihailovic, P.M.; Petricevic, S.J.; Radunovic, J.B. Compensation for Temperature-Dependence of the Faraday Effect by Optical Activity Temperature Shift. IEEE Sens. J. 2013, 13, 832–837. [Google Scholar] [CrossRef]
  20. Zhao, H.; Sun, F.; Yang, Y.; Cao, G.; Sun, K. A novel temperature-compensated method for FBG-GMM current sensor. Opt. Commun. 2013, 308, 64–69. [Google Scholar] [CrossRef]
  21. Yu, Q.; Li, X.-G.; Zhou, X.; Chen, N.; Wang, S.; Li, F.; Lv, R.-Q.; Nguyen, L.V.; Warren-Smith, S.C.; Zhao, Y. Temperature Compensated Magnetic Field Sensor Using Magnetic Fluid Filled Exposed Core Microstructure Fiber. IEEE Trans. Instrum. Meas. 2022, 71, 1–8. [Google Scholar] [CrossRef]
  22. Wang, X.; Lv, R.; Zhao, Y.; Zhao, J.; Lin, Z. Temperature-compensated optical fiber magnetic field sensor with cascaded femtosecond laser micromachining hollow core fiber and fiber loop. Opt. Laser Technol. 2023, 157, 108748. [Google Scholar] [CrossRef]
  23. Zhou, Y.; Liu, X.; Fan, L.; Liu, W.; Xing, E.; Tang, J.; Liu, J. Temperature and vibration insensitive fiber optic vector magnetic field sensor. Opt. Commun. 2022, 530, 129178. [Google Scholar] [CrossRef]
  24. Reilly, D.; Willshire, A.J.; Fusiek, G.; Niewczas, P.; McDonald, J.R. A Fiber-Bragg-Grating-Based Sensor for Simultaneous AC Current and Temperature Measurement. IEEE Sens. J. 2006, 6, 1539–1542. [Google Scholar] [CrossRef]
  25. Li, C.; Ning, T.; Wen, X.; Li, J.; Zhang, C.; Zhang, C. Magnetic field and temperature sensor based on a no-core fiber combined with a fiber Bragg grating. Opt. Laser Technol. 2015, 72, 104–107. [Google Scholar] [CrossRef]
  26. Su, G.-H.; Shi, J.; Xu, D.-G.; Zhang, H.-W.; Xu, W.; Wang, Y.-Y.; Feng, J.-C.; Yao, J.-Q. Simultaneous Magnetic Field and Temperature Measurement Based on No-Core Fiber Coated with Magnetic Fluid. IEEE Sens. J. 2016, 16, 8489–8493. [Google Scholar] [CrossRef]
  27. Sun, C.; Wang, M.; Dong, Y.; Ye, S.; Jian, S. Simultaneous measurement of magnetic field and temperature based on NCF cascaded with ECSF in fiber loop mirror. Opt. Fiber Technol. 2019, 48, 45–49. [Google Scholar] [CrossRef]
  28. Xu, R.; Xue, Y.; Xue, M.; Ke, C.; Ye, J.; Chen, M.; Liu, H.; Yuan, L. Simultaneous Measurement of Magnetic Field and Temperature Utilizing Magnetofluid-Coated SMF-UHCF-SMF Fiber Structure. Materials 2022, 15, 7966. [Google Scholar] [CrossRef]
  29. Huang, Y.; Qiu, H.; Deng, C.; Lian, Z.; Yang, Y.; Yu, Y.; Hu, C.; Dong, Y.; Shang, Y.; Zhang, X.; et al. Simultaneous measurement of magnetic field and temperature based on two anti-resonant modes in hollow core Bragg fiber. Opt. Express 2021, 29, 32208–32219. [Google Scholar] [CrossRef]
  30. Eftimov, T.; Dyankov, G.; Kolev, P.; Vladev, V.; Kolaklieva, L. A polarimetric fiber optic current sensor based on Bi12SiO20 crystal fluorescence. Opt. Mater. 2022, 133, 112837. [Google Scholar] [CrossRef]
  31. Eftimov, T.; Dyankov, G.; Kolev, P.; Vladev, V. A simple fiber optic magnetic field and current sensor with spectral interrogation. Opt. Commun. 2023, 527, 128930. [Google Scholar] [CrossRef]
  32. Lauer, R.B. Photoluminescence in Bi12SiO20 and Bi12GeO20. Appl. Phys. Lett. 1970, 17, 178. [Google Scholar] [CrossRef]
  33. Eftimov, T.; Dyankov, G.; Arapova, A.; Kolev, P.; Vladev, V. Temperature stability of a polarimetric current sensor based on BSO crystal fluorescence. In Proceedings of the 27th International Conference on Optical Fiber Sensors, Alexandria, VA, USA, 29 August–2 September 2022. [Google Scholar]
Figure 1. Polarimetric current sensor setup: (a) experimental arrangement, (b) side view of the BSO crystal used with dimensions, (c) top view of fluorescence and scattering with white LED illumination and (d) front views of fluorescence with 385 nm and 440 nm illumination via a large core optical fiber.
Figure 1. Polarimetric current sensor setup: (a) experimental arrangement, (b) side view of the BSO crystal used with dimensions, (c) top view of fluorescence and scattering with white LED illumination and (d) front views of fluorescence with 385 nm and 440 nm illumination via a large core optical fiber.
Sensors 23 09306 g001
Figure 2. Spectral response of the polarimetric sensor: (a) as analyzer angle increases from 0° to 90°; (b) as current in the coil increases from −28 A to +28 A.
Figure 2. Spectral response of the polarimetric sensor: (a) as analyzer angle increases from 0° to 90°; (b) as current in the coil increases from −28 A to +28 A.
Sensors 23 09306 g002
Figure 3. Interrogation techniques: (a) extrema wavelength shift; (b) π−shifted differential shift.
Figure 3. Interrogation techniques: (a) extrema wavelength shift; (b) π−shifted differential shift.
Sensors 23 09306 g003
Figure 4. Spectral responses of the extrema shift interrogation technique: (a) wavelength shifts of the maxima M1, M2, M3 and the minima m1 and m2, (b) wavelength dependence of the sensitivities SI(λ).
Figure 4. Spectral responses of the extrema shift interrogation technique: (a) wavelength shifts of the maxima M1, M2, M3 and the minima m1 and m2, (b) wavelength dependence of the sensitivities SI(λ).
Sensors 23 09306 g004
Figure 5. Normalized differential responses of the π-shifted interrogation technique: (a) responses of the maxima M1, M2, M3 and the minima m1 and m2, (b) wavelength dependence of the sensitivities ПI(λ) around the maxima M2, M3 and the minima m1 and m2.
Figure 5. Normalized differential responses of the π-shifted interrogation technique: (a) responses of the maxima M1, M2, M3 and the minima m1 and m2, (b) wavelength dependence of the sensitivities ПI(λ) around the maxima M2, M3 and the minima m1 and m2.
Sensors 23 09306 g005
Figure 6. Experimental setup.
Figure 6. Experimental setup.
Sensors 23 09306 g006
Figure 7. Temperature and spectral dependences of the optical rotation without magnetic field (I = 0): (a) rotation angle vs. temperature at different wavelengths; (b) wavelength dependence of the optical activity ρ(λ) at room temperature (22 °C); (c) temperature corrections Δρ to the optical activity with respect to the response from (b) at room temperature; (d) thermal coefficient aρ.
Figure 7. Temperature and spectral dependences of the optical rotation without magnetic field (I = 0): (a) rotation angle vs. temperature at different wavelengths; (b) wavelength dependence of the optical activity ρ(λ) at room temperature (22 °C); (c) temperature corrections Δρ to the optical activity with respect to the response from (b) at room temperature; (d) thermal coefficient aρ.
Sensors 23 09306 g007
Figure 8. Spectral and temperature dependence of the magneto-optical rotation without: (a) V(λ)L; (b) the maximum thermally induced variations over a 90 °C temperature range.
Figure 8. Spectral and temperature dependence of the magneto-optical rotation without: (a) V(λ)L; (b) the maximum thermally induced variations over a 90 °C temperature range.
Sensors 23 09306 g008
Figure 9. Two responses of the polarimetric sensor for the analyzer turned at 0° and 90° given by the thin line. The thick line is a theoretical fitting to the response at 0° from (18).
Figure 9. Two responses of the polarimetric sensor for the analyzer turned at 0° and 90° given by the thin line. The thick line is a theoretical fitting to the response at 0° from (18).
Sensors 23 09306 g009
Figure 10. Responses to current changes: (a) shifts of the extremum wavelength vs. current changes from −100 A to 100 A; (b) wavelength dependence of the sensitivity to current SI(λ); (c) the temperature dependence of the coefficient A0(T) from (22a); (d) the temperature coefficient A1(T).
Figure 10. Responses to current changes: (a) shifts of the extremum wavelength vs. current changes from −100 A to 100 A; (b) wavelength dependence of the sensitivity to current SI(λ); (c) the temperature dependence of the coefficient A0(T) from (22a); (d) the temperature coefficient A1(T).
Sensors 23 09306 g010
Figure 11. Temperature dependence: (a) Temperature induced wavelength shifts of four minima at I = 0A; (b) Wavelength dependence of sensitivities to temperature ST(λ) for different currents; (c) temperature dependence of the B0 coefficient from (23a); (d) the thermal coefficient B1from (23).
Figure 11. Temperature dependence: (a) Temperature induced wavelength shifts of four minima at I = 0A; (b) Wavelength dependence of sensitivities to temperature ST(λ) for different currents; (c) temperature dependence of the B0 coefficient from (23a); (d) the thermal coefficient B1from (23).
Sensors 23 09306 g011aSensors 23 09306 g011b
Figure 12. A linear fit for the orrespondence between calculated current and preset current: (a) for the (λ1, λ3) pair; (b) for the (λ2, λ3) pair.
Figure 12. A linear fit for the orrespondence between calculated current and preset current: (a) for the (λ1, λ3) pair; (b) for the (λ2, λ3) pair.
Sensors 23 09306 g012
Figure 13. A third degree polynomial fit for the orrespondence between calculated current and preset current: (a) for the (λ1, λ3) pair; (b) for the (λ2, λ3) pair.
Figure 13. A third degree polynomial fit for the orrespondence between calculated current and preset current: (a) for the (λ1, λ3) pair; (b) for the (λ2, λ3) pair.
Sensors 23 09306 g013
Table 1. Coefficients for the expressions for the sensitivities SI and ST.
Table 1. Coefficients for the expressions for the sensitivities SI and ST.
A00
(nm/A)
A01
(nm/°C/A)
A10
(1/A)
A11
(1/°C /A)
B00
(nm/°C)
B01
(nm/°C/A)
B10
(1/°C)
B11
(1/°C/A)
2.8 × 10−2−3 × 10−52.548 × 10−42 × 10−72.1 × 10−3−2.05 × 10−5−9.97 × 10−58.2 × 10−8
Table 2. Coefficients of the linear and third-order polynomial fits for the correspondence plots of the calculated Ic versus preset value of the current I.
Table 2. Coefficients of the linear and third-order polynomial fits for the correspondence plots of the calculated Ic versus preset value of the current I.
PairsLinearThird-Order Polynomial
1, λ3)Ic = 0.9438 I + 2.1467 (R2 = 0.9947)Ic = 1 × 10−5 I3 – 0.0009 I2 + 0.8612 + 5.9436 (R2 = 0.999)
2, λ3)Ic = 0.9318 I + 12.041 (R2 = 0.9981)Ic = 9 × 10−6 I3 – 0.0009 I2 + 0.8594 + 15.139 (R2 = 0.9947)
OverallIc = 0.9346 I + 6.8511 (R 2= 0.9958)Ic = 1 × 10−5 I3 – 0.0009 I2 + 0.8603 + 6.8511 (R2 = 0.9997)
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Eftimov, T.; Dyankov, G.; Kolev, P.; Vladev, V. A Spectrally Interrogated Polarimetric Optical Fiber Sensor for Current Measurement with Temperature Correction. Sensors 2023, 23, 9306. https://doi.org/10.3390/s23239306

AMA Style

Eftimov T, Dyankov G, Kolev P, Vladev V. A Spectrally Interrogated Polarimetric Optical Fiber Sensor for Current Measurement with Temperature Correction. Sensors. 2023; 23(23):9306. https://doi.org/10.3390/s23239306

Chicago/Turabian Style

Eftimov, Tinko, Georgi Dyankov, Petar Kolev, and Veselin Vladev. 2023. "A Spectrally Interrogated Polarimetric Optical Fiber Sensor for Current Measurement with Temperature Correction" Sensors 23, no. 23: 9306. https://doi.org/10.3390/s23239306

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop