ALC外壁の寒冷地適用性に関する研究
金崎 俊造長谷川 寿夫
著者情報
ジャーナル フリー

1995 年 60 巻 478 号 p. 27-33

詳細
抄録

We set up seventeen types of ALC external walls in three conditions of outdoor temperature (0, -10, -20 ℃ : constant) and three conditions of indoor air humidity (40, 60, 80 % R. H. in 20℃) for thirty days, and measured the quantity of vapor flowed into ALC external walls from indoor and the quantity of internal condensation of ALC external walls. As the outdoor temperature lowered and the indoor air humidity is higher, the quantity of flowing vapor and internal condensation increased. On this point, a simple ALC walls (50mm thickness) is typical. As the outdoor temperature lowered, most of flowing vapor into wall accumulated inside wall.