植物暴露実験用のPAN濃度自動制御システム
戸部 和夫高木 博夫大政 謙次
著者情報
ジャーナル フリー

1991 年 47 巻 2 号 p. 91-94

詳細
抄録

Peroxyacetyl nitrate (PAN) concentration was automatically controlled in a PAN expoeure system for plant to enable accurate PAN exposure experiments to be carried out effectively.
Gaseous PAN generated by bubbling nitrogen into a dilute PAN solution was introduced to air stream which blowed into an exposure box. The PAN concentration in the exposure box was measured with a chemiluminescent NOx analyzer continuosly and with an electron capture detection gas chromatograph (ECD-GC) at 7-min intervals. The PAN concentration was controlled with a computer as follows: (1) the flow rate of nitrogen introduced into the PAN solution was PID-controlled continuously to maintain a constant NOx analyzer response between ECD-GC outputs; (2) the NOx analyzer was recalibrated for PAN concentration at 7-min intervals by ECD-GC.
Using this system, PAN concentration in exposure air was kept within a range of ±5% deviation from a desired set point in the major time course of an experiment.