About the journal

Cobiss

Thermal Science 2022 Volume 26, Issue 3 Part A, Pages: 2043-2052
https://doi.org/10.2298/TSCI201205177C
Full text ( 2173 KB)
Cited by


Performance improvement of an industrial control enclosure cooling system

Chiang Wei-Ming (Graduate institute of Precision Manufacturing, National Chin-Yi University of Technology, Taichung, Taiwan)
Wang Fu-Jen (Department of Refrigeration, Air Conditioning and energy Engineering, National Chin-Yi University of Technology, Taichung, Taiwan), fjwang@ncut.edu.tw
Kusnandar (Graduate institute of Precision Manufacturing, National Chin-Yi University of Technology, Taichung, Taiwan + Department of Refrigeration and Air Conditioning Engineering, Politeknik Negeri Indramayu, Indramayu, Indonesia)

Following the trend of high accuracy machining, thermal management of industrial control enclosures become a critical issue. Therefore, a well-designed enclosure cooling system is essential to manage the heat generation inside the enclosure. In this study, to improve the performance of cooling system and the air-flow distribution inside the enclosure, CFD simulation has been used to evaluate the application of using the auxiliary circulation fan and air baffler. Furthermore, this study also investigates the lay-out design for both supply air vent and return air vent arrangement by two types of commercialized cooling systems through field measurements. The simulation results show the short circulation of air-flow is improved when the air baffler is installed. It also shows that the auxiliary circulation fan is suggested. Besides, air baffler is used to enhance the temperature distribution. The experimental results reveal the upper supply vent arrangement will cause the short circulation of air-flow slightly. The auxiliary circulation fans can improve the heat dissipation of cooling systems. There is no short circulation of air-flow for the lower supply vent arrangement, but the supply air cannot be distributed smoothly by the auxiliary circulation fans because the shape of the air baffler is not properly designed.

Keywords: Cooling system, industrial control enclosure, CFD simulation, air-flow distribution, temperature distribution