電気学会論文誌B(電力・エネルギー部門誌)
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
磁気浮上式鉄道のき電系における開閉サージ過電圧
村岸 一中村 佳明長岡 直人雨谷 昭弘
著者情報
ジャーナル フリー

1997 年 117 巻 5 号 p. 724-730

詳細
抄録

This paper investigates switching surge overvoltages due to a section switchgear between coils and a feeding cable, and surge overvoltages due to a ground fault in the feeding cable. The maximum overvoltage due to switchgear closing is about 25kV on the coil and 15kV on the cable sheath. The coil overvoltage becomes greater as a source voltage reaches its peak. The overvoltages due to switchgear breaking is dependent on a breaking current, and reaches 115kV on the coil and 15kV on the cable sheath when the current is 50A. The fault surge overvoltage is about 24kV on the coil which is smaller than the switching overvoltage. On the contrary, the cable sheath overvoltage reach 32kV which is the largest among various overvoltages investigated in the paper, and could result in sheath insulation breakdown. The coil overvoltage due to current breaking by a section switchgear may cause coil insulation breakdown when the breaking current is large. Both the coil and sheath overvoltages can be controlled to less than the insulation level by arresters.

著者関連情報
© 電気学会
前の記事 次の記事
feedback
Top