2011 年 131 巻 6 号 p. 421-426
A sudden capacity increase in demand during the summer peak, or in contingencies such as malfunctioning transformers, may cause overload for normal transformers. In this paper, on the basis of examples of overloaded transformer operation in distributing substations, thermal aging testing in oil was carried out under various overload patterns, such as short time overload and long time overload, but with the winding insulation paper's life loss kept constant. From the results, various characteristics such as mean degree of polymerization and productions of furfural and (CO2+CO), and their effects on the life loss of the insulation paper were obtained.