建築構造体の接地抵抗測定補正手法の検討 -その1. 半球状電極の場合ー
森田 祐志上田 早紀高橋 健彦
著者情報
ジャーナル フリー

2011 年 31 巻 2 号 p. 150-155

詳細
抄録

The fall of potential method is generally used for measuring the earthling resistance. This method needs two auxiliary electrodes and it is required that two auxiliary electrodes are placed at enough distances from the earthling electrode,e. g. building foundation. However, in urban area there is not enough space for taking measurement. So,it is very difficult to measure the earth resistance precisely. However,there is the 4-potential method when it stand on the theory of the fall of potential method. It is purposed of this paper to basic study on correction method of measured earthling resistance by 4-potential method.