Using Computational Fluid Dynamics Simulation to Perform Fire Investigation

Article Preview

Abstract:

Fire occurred evening 10th July 1989 at Terwindle Rest Home Auckland. Incident report shows that this fire resulted in seven fatalities and extensive fire damage to the building. The primary cause of the death was carbon monoxide poising from smoke inhalation. The fire started at the lounge which contained ten upholstered couches with polyurethane foam padding. Sprinkler fire protection system was not installed and the building has no smoke detection system (based on the New Zealand Building code requirement that was imposed at that time). In this study, the fire is modeled using Computational Fluid Dynamics (CFD) software FDS (Fire Dynamic Simulator). The heat release rate of the fuel burned was obtained from lab measurement of a sofa. The results were validated against the approximate time scale of the progress of the fire as it was found from the fire investigation report. It has been found that FDS can provide accurate simulation to the fire which can be used to perform fire investigation provided that the correct heat release rate of the fire used in the model.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

845-850

Citation:

Online since:

September 2013

Export:

Price:

[1] P. Byrne, Terwindle Rest Home – Fire analysis computer simulation, New Zealand Fire Service, 1994, Wellington, New Zealand.

Google Scholar

[2] B. Karlsson, J. G Quintiere, Enclosure fire dynamics. 2000, CRC Press, USA.

Google Scholar

[3] F. F. Chen, Radiant Ignition of New Zealand Upholstered Furniture Composites, Master of Engineering in Fire Engineering Thesis, 2001, The University of Canterbury, New Zealand.

Google Scholar

[4] M. J. Spearpoint, (ed), Fire engineering design guide" Centre for Advanced Engineering, 2008, Third Edition, University of Canterbury, New Zealand.

Google Scholar

[5] D. A. Purser, Toxicity Assessment of Combustion Products, Chapter 2-6, SFPE Handbook of Fire Protection Engineering, 2002, Third Edition, Society of Fire Protection Engineers, USA.

DOI: 10.1007/978-1-4939-2565-0_62

Google Scholar

[6] PD 7974-6, The application of fire safety engineering – Principles to fire safety design building- human factors: Life safety strategies- occupant evacuation, behaviour and condition, 2004, British Standards.

DOI: 10.3403/03067582