Thermal Aging Effects on Fire Performance of the Cross-Linked Polyethylene Insulated Cable

Article Preview

Abstract:

To evaluate the fire performance of the cable in service, the ignition time, heat release rate and insulation failure parameters of the accelerated thermal aging cable on stimulated fire condition were studied. The results show that, the extended ignition time and decreasing peak of heat release rate of the cable in the early stage of aging are the addictive including the lubricant, plasticizer and anti-oxygen. In the aggravating of thermal aging, labile materials with low heating value will be exhausted, while the thermal stability of insulation sheath material decreases, its corresponding ignition time will start to shorten and initial peak of heat release rate will start to rise. The insulation failure temperature of the cable is related with the decomposition temperature of insulation materials of the cable by heating. In each aging stage, the decomposition temperatures of insulation materials by heating are all lower than the insulation failure temperature of the cable for about 10°C. The reason for the insulation failure of the cable is that the ambient heat , gives rise to the decomposition by heating of internal insulation materials of the cable through sheath materials finally under the thermal transmission effect.

You might also be interested in these eBooks

Info:

Periodical:

Pages:

2399-2404

Citation:

Online since:

June 2017

Export:

Price:

* - Corresponding Author

[1] Sener, Ahmet Akin, Enver Demirhan, The investigation of using magnesium hydroxide as a flame retardant in the cable insulation material by cross-linked polyethylene, Materials & Design 29. 7 (2008) 1376-1379.

DOI: 10.1016/j.matdes.2007.05.008

Google Scholar

[2] Li, Lu, An enhanced fire hazard assessment model and validation experiments for vertical cable trays, Nuclear Engineering and Design 301 (2016) 32-38.

DOI: 10.1016/j.nucengdes.2015.12.034

Google Scholar

[3] Babrauskas, Vytenis, Electrical fires, SFPE Handbook of Fire Protection Engineering. Springer New York, (2016) pp.662-704.

DOI: 10.1007/978-1-4939-2565-0_22

Google Scholar

[4] Zhang Jun, Ji Kuijiang. Polymer combustion and flame retardant technology, Chemical Industry Press, Beijing (2001) 420- 425.

Google Scholar

[5] Babrauskas V., Richard D. Peacock, Heat release rate: the single most important variable in fire hazard, Fire safety journal, 18 (1992) 255-272.

DOI: 10.1016/0379-7112(92)90019-9

Google Scholar

[6] Zhang Xiang, Li Feng, Liu Songlin, Exploration on the study of wire and cable flammability by using cone calorimeter, Fire Science and Technology, 26(2007) 262-264.

Google Scholar

[7] Wang Wei, Zhang Heping, Wan Yutian, A study on the burning behavior of PVC cables in the conic calorimeter test, Journal of Safety and Environment, 8(2008) 117-120.

Google Scholar

[8] Zhang Xiang, Li Feng, Wang Yuzhong, Ye Shimao, Peng Bo, Study on thermal degradation kinetics of fire retardant PVC for cable insulation, Insulating Material, 40(2007) 52- 56.

Google Scholar

[9] Lin, Yan J, Modulating effect of Mg-Al-CO3 layered double hydroxides on the thermal stability of PVC resin, Polymer Degradation and Stability, 88 (2005) 286-293.

DOI: 10.1016/j.polymdegradstab.2004.11.007

Google Scholar

[10] Leszczyńska, A., Polymer/montmorillonite nanocomposites with improved thermal properties: Part I. Factors influencing thermal stability and mechanisms of thermal stability improvement, Thermochimica Acta, 453 (2007) 75-96.

DOI: 10.1016/j.tca.2006.11.002

Google Scholar