After simulation of 168 cases (42 for the base scenario and 126 for the controlled scenario), the obtained results are presented in this section.
4.2. Parametric Analysis
The performance of the KPIs defined in the corresponding section is described in the following section. The so-called violin-plots have been used to capture the distribution of these parameters. This kind of graph adds another dimension that involves the frequency of the values: the more values there are in that area, the wider the graph is. For this parametric analysis, the violin-plot is divided into two halves: the left one captures the base case scenario and the right one captures the scenario in which the controller is enabled. Quartiles (colored areas) and mean values (crosses) are also represented.
It is necessary to consider that the main objective of the implemented rule-based control is to increase the self-consumption of the system. Thus, the mean self-consumption ratio is improved in every climate. The improvements are all between 9.7% (Cordoba) and 15.3% (Berlin), as can be seen in
Figure 17.
By analyzing the effect independently and starting with the building insulation, OHH obtains slightly better self-consumption ratios. This can be explained by the fact that, in buildings where the heating demands are higher, it is easier to find days in which the indoor temperature has room to be boosted during the central part of the day, when the PV production is higher. Thus, the electrical power coming from the PV panels is consumed by the heat pump, increasing the self-consumption ratio, as shown in
Table 4.
Regarding the minimum excess value and the installed PV power, the effect is more evident. In
Figure 18, the improvements in self-consumption in Berlin for NHH are shown. First, it can be seen that the higher the minimum PV excess, the lower the self-consumption improvement is. This effect is derived from the non-self-consumed power as the activation criteria become stricter. In other words, if the minimum excess value is 1800 W instead of 1400 W, the rule-based controller is enabled for a shorter amount of time, which decreases the self-consumption of the system.
Furthermore, concerning the PV power installed in the building, greater improvements are achieved with larger PV installations. This is mainly due to the low-base scenario self-consumption ratios. Since the PV generation and the heat pump consumption are independent, large PV installations obtain worse self-consumption ratios if no control is implemented. When a certain control is inserted, a larger percentage of improvements are obtained.
Furthermore, the higher the PV installation, the smaller the effect of the minimum excess value. If the PV installation is large, the percentage difference between two certain minimum excess values becomes smaller, and therefore, so does the improvement in the self-consumption ratio.
The effect seen for the self-consumption ratio can also be observed when analyzing the yearly consumed electricity cost of the HP. These differences are shown in
Figure 19. The larger savings are the ones seen in Albacete (4.7%), in which there are important heating and cooling demands throughout the whole year, as seen in
Table 1. For the remaining cities, reductions of between 1.5% and 3.5% are observed.
Furthermore, the reduction seen in the absolute cost is also transferred to the specific cost. That is, when the controller is enabled, the system is able to provide heat at a lower price. These reductions can be seen in
Figure 20. Comparing both the cost and the specific cost, the same trends can be derived: the larger reductions are obtained in Albacete (9.8%), while for the rest of the locations, reductions of between 3.8% and 7.8% are seen.
Despite having a positive impact on both the self-consumption ratio and the cost, an effect that is often neglected when studying this kind of controller is the extra amount of both heat and electric power that is being consumed by the heat pump. These effects are shown in
Figure 21 and
Figure 22, respectively. These increments of both the provided heat and the consumed power can be understood as a potential downside of this kind of controller, since it is a non-explicitly desired result (although the extra amounts of energy do not have a negative economic impact for the final user).
Since the algorithm on which the controller is based aims to maximize the self-consumption, it turns on the heat pump when all the base demands are fulfilled. When that happens, new temperature set-points are applied: higher values for heating demands and lower values for cooling demands, which leads to more consumed power.
Figure 23 shows how the cumulative distribution of the mean temperature in the condenser (understood as the arithmetical average between the input water temperature and the output water temperature) is different for the base case and the controlled scenario. When the controller is enabled, it is more common to have condenser temperatures of around 32–50 °C, caused by the new set-points of the space heating mode. The effect of the new temperature for the DHW is not that remarkable though, mainly because the activations of the heat pump in that mode are shorter and are not long enough to reach a steady-state situation.
The implemented algorithm not only changes the set-points of the tanks, but also the indoor temperature: fixing higher set-points in winter and lower ones in summer. The effect of changing these values is subjective and their potential impact on the comfort sensation may be hard to study numerically. Although it may be said that everything that deviates from the so-called standard set-points is a non-desired effect, the opposite might also be argued. That is, the user chooses more relaxed standard set-points in order to completely fulfill their comfort criteria only when the excess mode is enabled.
However, there will surely be a difference in the temperature distribution if the controller is activated. This effect can be seen in
Figure 24 (for winter months) and
Figure 25 (for summer months) for Albacete.
As can be observed, in
Figure 24 (winter months), temperatures between 23 °C and 24 °C are more common when the controller is enabled. When compared to the base case scenario, the probability distribution seems to be moved 1 K to the right-hand side. On the other hand, in
Figure 25 (summer months), it is clear how the temperature distribution is moved to lower temperature values.
In addition, once all the simulations were carried out, a regression analysis was carried out with two objectives. Firstly, to quantify the effect of each of the analyzed parameters on the final outcome in terms of self-consumption; and secondly, to derive a relatively straightforward equation that could be used to obtain an approximation of the operation of the system and the controller in other scenarios.
Thus, the expression for the self-consumption ratio, shown in Equation (3), is proposed. Its inputs are the minimum photovoltaic excess to activate the excess mode (
), the yearly photovoltaic generation (
), the yearly average temperature (
), the yearly average horizontal solar irradiation (
), the heating demand per unit area (
), and the cooling demand per unit area (
).
The derived coefficients can be seen in
Table 5, while
Figure 26 shows the comparison between the real and predicted values calculated by the linear regression. The dashed lines represent deviations of 8%. The model gives a root-mean-square error (RMSE) of 0.0189.
Nevertheless, the above equation is not useful for sorting out the impact of each of the variables, since it does not consider the range of the variables. Therefore, all variables have been normalized between 0 and 1, and the new coefficients are shown in
Table 6 and
Figure 27.
From the analysis, it can be deduced that, within the cases that have been simulated, the most important variable when it comes to the self-consumption ratio obtained when the rule-based controller is enabled, is the heating demand per unit area. Considering only that variable, the higher the heating demand, the better the indicator will perform. This effect has been mentioned previously and is related to the fact that, in buildings with larger heating demands, the indoor temperature may go down during the central hours of the day. Thus, the controller has room to raise the temperature by switching on the heat pump and consuming the power that comes from the PV installation.
The total energy produced by the PV system has a similar coefficient, but with a negative sign. That is, the larger the PV generation, the smaller the self-consumption ratio will be. In systems where the PV installation is larger, not all the power coming from the panels can be consumed, not even when the controller is on.
In addition, the cooling demand per unit area comes with a positive sign, as do the mean irradiation and temperature. Finally, the minimum PV excess value to activate the excess mode is introduced with a negative impact. That is, with large values, the self-consumption goes down, but its impact is smaller than the heating demand, for example.
Furthermore, to deduce a more precise regression, interactions between variables have been introduced in the model. That is, with this approach, terms that consider the multiplication between variables are included: the result is an equation that contains 22 terms. By doing so, the model becomes more complicated, but it is able to better capture the performance of the self-consumption ratio. It has an RMSE of 0.0087. The results are shown in
Figure 28, while the coefficients are set out in
Table 7.