IEEJ Transactions on Power and Energy
Online ISSN : 1348-8147
Print ISSN : 0385-4213
ISSN-L : 0385-4213
Special Issue Paper
Induced Surge Characteristics from a Counterpoise to an Overhead Loop Circuit
Toshio SonodaYasuo TakeuchiShozo SekiokaNaoto NagaokaAkihiro Ametani
Author information
JOURNAL FREE ACCESS

2003 Volume 123 Issue 11 Pages 1340-1349

Details
Abstract

This paper surveys disturbances experienced in the low-voltage control circuits of the power stations and the substations of Kansai Electric Power. Induced voltages to an overhead control cable from a grounding mesh were measured when an impulse current was applied to the grounding mesh. A non-metallic sheath cable (CVV cable) and a cable with a metallic sheath (CVV-S cable) were tested to investigate the effect of the metallic sheath on the induced voltage to the cable. Then, a simulation model of the transient induced voltage to the overhead conductor from a counterpoise was proposed. Finally, the simulation results were compared with the measured results to confirm the accuracy of the proposed method.

Content from these authors
© 2003 by the Institute of Electrical Engineers of Japan
Previous article Next article
feedback
Top