R22/R114系混合冷媒を用いたヒートポンプシステムに関する研究 : 第2報, 内面溝付管の二重管熱交換器を用いた実験
高松 洋小山 繁池上 康之屋良 朝康喜多村 稔藤井 哲
著者情報
ジャーナル フリー

1991 年 57 巻 539 号 p. 2377-2382

詳細
抄録

The performance of a vapor compression heat pump system is tested using R22/R114 mixtures as the working fluid. Double pipe heat exchangers, where the refrigerant flows inside the inner tube with grooved internal surface and water flows countercurrently in the outer annulus, are used for the condenser and evaporator. Experimental results are compared with those for the same system with a smooth tube condenser and the evaporator presented before. The effect of the superheating of the refrigerant at the exit of the evaporator on COP is also discussed. A trial calculation based on the experimental results shows that the COP of the mixture becomes larger than that of the pure refrigerant in the case of a large change in the water temperature only if the heat transfer surface area is large enough and the superheating of the refrigerant is quite small at the exit of the evaporator.