Measurement of the Dielectric Recovery Strength and Reignition of AC Contactors

Degui CHEN
Xingwen LI
Ruicheng DAI

Publication
IEICE TRANSACTIONS on Electronics   Vol.E88-C    No.8    pp.1641-1646
Publication Date: 2005/08/01
Online ISSN: 
DOI: 10.1093/ietele/e88-c.8.1641
Print ISSN: 0916-8516
Type of Manuscript: Special Section PAPER (Special Section on Recent Development of Electro-Mechanical Devices--Selected Papers from International Session on Electro-Mechanical Devices 2004 (IS-EMD2004)--)
Category: Contactors & Circuit Breakers
Keyword: 
contactors,  dielectric recovery strength,  reignition,  measurement,  

Full Text: PDF(754.5KB)>>
Buy this Article



Summary: 
In order to understand the recovery characteristics of AC contactors and improve their performance, experimental measurements were used to investigate the arcing gap recovery process including dielectric recovery strength and reignition, to a pair of splitter plate together and four kinds of arc chamber of AC contactors. A special circuit was designed to perform the work. It demonstrates that under lower current, the dielectric recovery strengths of all kinds of arc chambers in the paper have no significant difference. However, with the increase of current, the difference of dielectric recovery strengths of them is much clear. The reignition characteristics of a pair of splitter plate and arc chambers are similar. With different configurations of arc chambers and prospective currents, the forms of post current zero reignition are distinct.