Methods of determining safety boundary and PPE by analysing arc-flash incident energy in medium voltage panels

, and

Published under licence by IOP Publishing Ltd
, , Citation A Mashar et al 2020 IOP Conf. Ser.: Mater. Sci. Eng. 830 032048 DOI 10.1088/1757-899X/830/3/032048

1757-899X/830/3/032048

Abstract

Arc-flash events still occur frequently in industries especially in Indonesia and there are many operators and technicians have got burn injuries caused by it. To avoid this accident, this paper discus about arc flash and its incident energy as well as personal protective equipment (PPE) should be worn by those working with electric panels (switchgears). To demonstrate how incident energy is calculated and the protection boundaries are determined, a 6 kV, 3750 kVA utility panel in a geothermal power plant (60 MW) is used as object. The steps have to be done in this research are bolted fault current and arc fault current calculations, calculation of incident energy and determining both protection boundaries and the relevant PPE. As result, it is found that with protection setting clearing time of 0,12, the incident energy is 4,418 J/cm2 and the protection boundary is 1.4 m. The danger will increase with longer clearing time of relay or closer distance to the panel. This paper will hopefully be very help full for the responsible engineers to analyse the danger of any kind of panels and to determine PPE for workers.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1757-899X/830/3/032048