Brought to you by:
Paper The following article is Open access

Numerical simulation research on the fire in cable cabin of utility tunnel with different longitudinal fire source locations

, , , , and

Published under licence by IOP Publishing Ltd
, , Citation Dewang Geng et al 2022 IOP Conf. Ser.: Earth Environ. Sci. 983 012063 DOI 10.1088/1755-1315/983/1/012063

1755-1315/983/1/012063

Abstract

A full-scale model was established by the Fire Dynamics Simulator (FDS) to study the fire characteristics in the cable cabin of utility tunnel with different longitudinal fire source locations. Five fire sources at different locations were placed in a 200-meter-long fire compartment. Several important parameters were obtained and analyzed, including temperature distribution, smoke concentration, and fire self-extinguishing. The results present that the fire source located at 1/2 of the longitudinal direction has the largest range of high-temperature smoke, which leads to the largest damage range of the concrete structure. The reverse filling of the smoke in the utility tunnel leads to the longitudinal CO peak concentration first decreasing and then increasing from the fire source to the end. When the fire source is located at 1/8 of the longitudinal direction, the fire self-extinguishing time is the longest. These encouraging results could provide significant references for the fire protection design and fire control of the utility tunnel.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1755-1315/983/1/012063