Paper The following article is Open access

Hybrid Modeling of Central Air-Conditioning Cold Source System Energy Consumption with K-means Cluster Algorithm

Published under licence by IOP Publishing Ltd
, , Citation Zhihao Zhou 2019 IOP Conf. Ser.: Earth Environ. Sci. 295 052035 DOI 10.1088/1755-1315/295/5/052035

1755-1315/295/5/052035

Abstract

Gray box model and artificial neural network (ANN) model of central air-conditioning cold source system have been established with simulation data to predict system operation energy consumption and compare the prediction accuracy difference of models under variable training data. A hybrid model is proposed to combine gray box model and ANN model based on K-means cluster algorithm. The results show that ANN model has higher prediction accuracy than gray box model when the membership of model input variables to trained input data is greater than 0.4. Otherwise, the gray box model has higher energy consumption prediction accuracy. Compared with gray box model and ANN model, prediction accuracy of hybrid model increases 27.7% and 33.85% on average under different training data.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.