Performance assessment of solar and desiccant aided building air-conditioning system

and

Published under licence by IOP Publishing Ltd
, , Citation Gaurav Singh and Ranjan Das 2023 J. Phys.: Conf. Ser. 2430 012004 DOI 10.1088/1742-6596/2430/1/012004

1742-6596/2430/1/012004

Abstract

Indoor thermal comfort significantly influences people's health, happiness and consequently the output at the workplace. Here, a systematic simulation study on a conventional vapor compression-based building cooling system integrated with desiccant assisted dedicated outdoor air system (DOAS) is performed using EnergyPlus software for warm and humid climate zones. Impact of using desiccant material in the DOAS, on the cooling load requirement of the building, coefficient of performance (COP), and energy consumption of the system is discussed. The building design is well-validated with the available guidelines. Desiccant assisted system supplies dehumidified air inside the building space which affects the evaporator performance. A flat plate solar collector system is used to supply the hot air to regenerate the desiccant material. Electric energy savings in desiccant assisted system can be achieved up to 5.5 %, whereas, the COP of the system is not found to be significantly affected even though thermal load demand reduces by nearly 13.5 % by the proposed modification.

Export citation and abstract BibTeX RIS

Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI.

Please wait… references are loading.
10.1088/1742-6596/2430/1/012004