Introduction

In 1969, Fazlur Khan first classified the structural system for designing of tall buildings. At that time rigid frame was the most dominating structural system that prevailed in that era for the design of tall buildings. Falzlur Khan first introduced a new structural system named tubular structural system and designed the Sears Tower, 108 story high world tallest building with it at that time.

Again in 2007, by Ali and Moon this structural system was re-classified (Ali and Moon 2007). These structural systems are classified depending upon the height of the building selected for designing. Other parameters like loading conditions, architectural requirement, site conditions and functional requirement are also imperative. For high-rise buildings he classified them as framed tube structure, diagrid building structural system, outrigger structure, bundled tube, tube in tube and frame with shear wall, etc.

This paper presents a detailed discussion about the shear lag effect, a major phenomena that controls the designing of tall building of tube structural system. Tube in tube with façade bracing system is used for designing the buildings of 120 stories high. Objective of this study is to study the shear lag effect and its correlation with stiffness-based design in tube structural system.

In tube structural system, buildings are designed considering a hollow concrete box projecting out of ground designed as a cantilever beam in which façade columns are spaced closer and connecting beams are considerably deep making it hollow box-like structure which supports the lateral loads (http://en.wikipedia.org/wiki/Tube_(structure); Ali and Moon 2007; Siavash 2001). This idea also comes from the nature of Bamboo tree which is very tall and thin. At each node, Bamboo is stiff enough resembling the stiffened diaphragm of a building (Mark 2011).

In this paper, one tube is provided at the outer periphery of the total plan area and another tube is provided inside the plan area in which core area used is 25 % of the total plan area. It is found that with this tube-in-tube structural system, top lateral deflection limit could be controlled with H/500 as an engineering decision (Mendis et al. 2007).

Shear lag effect and stiffness of a building

Loads on tall buildings can be divided into two vertical or gravity loads and lateral loads. Tubular structure is the most efficient structural system that utilizes both kinds of loads for designing a tall building. Providing column-free area between the core and the perimeter columns maximizes gravity loads coming on outer columns which increase building’s stability in overturning.

With the application of lateral load, column deflects in lateral direction and beam deflects in bending. This gives rotation of beam column joint. Because of the rotation of beam column joints, shear lag effect is induced in a building. Shear lag effect can be observed in any hollow box-like structural system which is loaded laterally. An example can be a hollow box girder that is used in the designing of bridges.

Motivation of this study stems out from the thinking that perhaps shear lag effect influences the design of tall buildings with tubular structural system. Controlling the shear lag can perhaps control the lateral deflection of the building. Theoretically, if the limit is reached of beam column joint rotation to be zero, panel starts behaving like a shear wall.

In this paper, shear lag effect is being studied and is correlated with stiffness of the building. Studies are also done for the different patterns of bracing systems. For convenience and to do relative study for shear lag effect, cross-sectional dimensions of beam and columns, their alignments (column) and the material properties are not changed with height of the building.

Literature review

Fazlur Khan in 1961 first had the idea of tube structural system. He first designed a 43-story DeWitt-Chestnut Apartment Building in Chicago. After that he designed world’s tallest building Sears Tower with nine-bundled tube in Chicago (http://en.wikipedia.org/wiki/Tube_(structure)). As the building becomes tall, say more than 60 stories, tubular structure itself becomes inefficient for withstanding lateral loads because of shear lag. It much more starts behaving like rigid frame structure. In which in web panels, bending deflection in beam and columns becomes high, consequently increasing the shear lag. To control these deflections and hence to increase the building’s stiffness, he suggested three different methods. One of which is by providing additional tube inside the building plan called tube-in-tube structural system. Second one is by providing bundled tube (Ali and Moon 2007). Third way of increasing the lateral stiffness of the structure is by providing bracing system which efficiently reduces the shear lag and increases the building performance to support the lateral loads.

In 2007, Johan Leonard presented his studies on shear lag effect in diagrid building structural system (Leonard 2007). He studied the shear lag effect in 60 stories high buildings by varying diagrid angles. He found that shear lag effect keeps on increasing as the angle of diagrid changes from 31° to 90°. In his studies top lateral deflection was found minimum for the diagrid angle of 63.4°–71.6°.

In 2007, K.S. Moon studied methods of designing diagrid building structural system (Moon 2008, 2009, 2012; Moon et al. 2007; Thomas and Viktor 2010). Theoretically he proved that for maximum shear rigidity of diagrid, optimal angle should be falling near 35°, but for maximum bending rigidity it should be at 90° from horizontal. So, optimal angle should fall between these two values, i.e., 35° and 90°. In the analysis he discovered that optimum diagrid angle for building of height from 60 to 20 stories falls between 53° and 76°. He also concluded that this optimal angle of diagrid decreases as the height of the building decreases.

K.S. Moon again carried out his studies on braced tube structural system of 100 story high building with various diagonal configurations. In his studies he found that diagonal angle of bracing between 35° and 55° is the best possible structural configuration for material-saving design (Moon 2012).

Shear lag effect

Shear lag effect in a building can be best understood with the help of Fig. 1. In this figure cross section of a building is shown in which a moment is induced because of the application of lateral load. Figure shows the theoretical and real distribution of axial stresses in peripheral columns. Now considering the whole structure as a cantilever beam, axial stress generated in the columns of outer periphery are the bending stresses. This statement follows with the theory of bending.

Fig. 1
figure 1

Axial stress distribution in the columns of the building in web as well as in flange panels

Again with the theory of bending, variation of these stresses along any panel (flange or web) must be varying linearly. Real distribution of these axial stresses in panels can be observed in the figure which is not linear. In the flange panel, magnitude of axial stress at the corner side is high in comparison to the columns of middle panel. So in the flange panel middle columns axial stress lags behind with that of the corner columns. Same kind of nonlinear distribution of axial stress can also be observed in the web panels. This kind of nonlinear distribution of axial stress along the flange and the web panels is called as shear lag effect.

To illustrate more a three-dimensional model of a cantilever beam of hollow square cross section resembling a tube is modeled with thin shell element in SAP 2000 (Fig. 2). The beam is 3 m long and cross-sectional dimensions are 0.5 m × 0.5 m. This beam is loaded with uniformly distributed load acting approximately till mid of its length as shown in figure.

Fig. 2
figure 2

Three-dimensional view of the finite element model of the cantilever beam 3 m long loaded with UDL till 1.71 m length from the fixed end

Type of loading resembles with the kind of wind load that is typically considered to act at each node laterally. Results are displayed for the loading till mid-length of the beam for better demonstrating the concept of positive and negative shear lag (Leonard 2007).

After running the analysis, the beam displayed the deformed shape. As stress is directly proportional to strain, so studying the deformed shape demonstrate the stress distribution in the beam.

In Fig. 3, its top flange deformation along the width is shown. These deformations are shown at regular intervals along the length of the beam. These deformations are magnified for better understanding. It can be observed that till length 0.85L, deformation in the corner part is more than the deformation in the mid-part of the flange. For the further length mid-portion of the flange is showing more deformation in comparison to the corner part.

Fig. 3
figure 3

Top flange deformation in the longitudinal direction

Fig. 4
figure 4

Perspective view of the ground story

Positive and negative shear lag, shear lag ratio

Near the fixed end of the cantilever beam, along the flange width, stresses are high in corner side in comparison to middle of the panel. This type of shear leg effect is called positive shear leg. Towards the free end, in the middle part of the flange, stresses are high in comparison to corner part of the flange. This type of shear lag is called negative shear lag.

Shear lag ratio is introduced to measure the magnitude of shear lag effect. It is the ratio of stress of maximum stress at the corner side of the flange panel to the middle of the panel where stress is least. This ratio tells the effect of shear lag in the panel. Less than one value of shear lag ratio describes the negative shear lag. Table 1 shows variation of shear lag ratio along length for this beam.

Table 1 Shear lag ratio in beam

Building modeling

For all buildings, plan area is 42 m × 42 m. At the outer periphery, columns are spaced at 3.5 m center to center and floor height is set as 3.5 m each. For controlling lateral deflection, a central core is also provided. Building’s façade beam–column connections are moment connections. Central core area is 25 % of the total plan area. Area between central core and building façade is column free which spans 10.5 m. Inner core column connects with outer peripheral columns with rigid diaphragm. Rigid diaphragm means that in-plane deformations are negligible, whereas out-of-plane deformations (in bending) are allowed. Now, in this tube-in-tube structure where diaphragm is rigid, entire lateral load is carried by the peripheral and inner core columns only. Wind load is applied according to IS 875, Part-3 (BIS 1987). Depending upon several factors like place, category of the terrain and class of structure selected, design wind speed for lateral load calculation is shown in Fig. 5. Building bracing systems are connected with pined connections. Cross-sectional dimensions of members of 120 story high building are shown in Table 2 (Fig. 4).

Fig. 5
figure 5

Design wind speed according to IS 875 for calculation of lateral load on building models

Table 2 Dimensions of the members for 120 story high building

Shear lag effect in a building

Objective of this paper is to study the shear lag for different heights of buildings and also to investigate it for different possible geometric patterns of bracing systems.

Figure 5 shows the shear lag effect in a 120 stories high framed tube-in-tube structural building. It can be seen in this building that at the bottom of the building there is positive shear lag effect. With increasing height, it continues to decrease till it becomes zero. For further height it converts to negative shear lag (Fig. 6).

Fig. 6
figure 6

Shear lag effect in 120 stories high building. Flange and web panels are shown

Fig. 7
figure 7

Variation of shear lag ratio versus the story number

In these results it is found that for 120 stories high building, value of shear lag ratio starts changing from positive to negative at around 30th story. For 96 stories high building, this change comes around at 25th story. For 72 stories high building, it is at 20th story and for 48 and 36 story high building it is around at 15th story.

Problem statement

Fulfilling the geometric requirement of the building, bracing systems are provided with an inclination of 45°, 63.43°, 71.56°, 75.96°, 80.53° and 84.28° from horizontal. With these geometric angles, each diagonal member meets with each column at beam column joint (Figs. 8, 9) in a panel. Buildings without braces are considered to have 0° angle. All possible geometric configuration of bracing systems are considered in this study (Fig. 7).

Fig. 8
figure 8

Bracing systems of different patterns considered in this study. Bracing angle is 45° from horizontal. Only 120 stories high buildings are shown

Fig. 9
figure 9

Buildings of model 1, different alignments of bracings in 120 stories high buildings are shown

Short buildings with low aspect ratio are expected to deform principally by shear action, whereas tall buildings of high aspect ratio are expected to deform principally by bending. Theoretical discoveries by Moon et al. (2007), optimal angle should lie between 35° and 90°. Now, objective of this study is to find the variation of shear lag as the height of the building changes. Also study the shear lag with the changing pattern of bracing systems and to correlate it with the overall stiffness of the building and hence to conclude about the overall performance of the buildings.

Optimum design strategy

Suppose B and L is the width and height of the building, respectively. With bracing angle θ from horizontal, total length of one bracing becomes (Fig. 10 )

$$= \, L/\sin (\theta ).$$
Fig. 10
figure 10

The length and width of the building with bracing of angle θ from horizontal are shown

If A is the cross-sectional area of bracing element then total volume of steel used for one single brace

$$= A \times L/\sin (\theta ).$$

Taking example of buildings of model 1, there are two bracing members in a panel and there are four such panels in a building. So total volume of steel used in this type of model is

$$= 4 \times 2 \times A \times L/\sin (\theta ).$$

As length of the building (L) as well as member cross-sectional area (A) remains same for a particular height, this volume of steel depends on the bracing angle θ only.

As angle changes from 0° to 90°, value of sin (θ) increases as can be observed in Fig. 11. Hence volume of steel used decreases with increasing values of θ.

Fig. 11
figure 11

Variation of sin (θ) with varying θ from 45° to 90°

So, material usage is minimum for bracing angle 84.28° and maximum for 45° but can be said as optimum for the angle for which lateral deflection of building is minimum.

Results and discussion

In a building, at the ground story columns, shear lag effect is most dominating and most influential because of large magnitude of axial stresses. For further analysis and comparison purpose shear lag ratio at ground story is considered for all heights and for all models.

Results for buildings of model 1

For this kind of bracing pattern, optimal angle for shear lag ratio lies between 45° and 63.43° for all heights of buildings. For 120, 96 and 72 story high buildings, 63.43° is the optimal angle and for 84 and 36 story high buildings, 45° is the optimal angle.

Now considering the graphs of Figs. 12 and 13 in which shear lag ratio and top lateral deflection, respectively, are varying versus the bracing angle. Comparing these variations, it seems almost parallel variation among the two. It represents that by providing this geometric pattern of bracing system, building’s stiffness varies the way shear lag varies in a building.

Fig. 12
figure 12

Variation of shear lag with varying angle of bracing system for buildings of model 1

Fig. 13
figure 13

Top lateral deflection versus varying angle of bracing system for buildings of model 1

Looking close to the geometric pattern of this bracing, at any cross section of a panel there are two bracing members and each goes through the panel from one end to another. In this type of geometric pattern load transfer path is most continuous to the ground.

Results for buildings of model 2

In this type of bracing pattern, diagonal members do not continue through the panel instead it ends in the middle of it. This way load transfer path does not continue through to the ground.

At the joint where two of the bracing members are meeting, axial load distributes among the bracing members, thereby decreasing the axial force in the middle of the column. At the other end, in the corner columns this axial force increases.

Shear lag ratio is nothing but the ratio of maximum to minimum axial stress in flange panel. This geometry affects more for shorter length or for small inclinations, whereas it decreases with increasing inclination. So shear lag ratio is suppose to be high for small inclinations of bracing angle and supposed to decrease as the angle of inclination increases. This variation can be observed in graphs of Fig. 14.

Fig. 14
figure 14

Variation of shear lag ratio with varying angle of bracing system for buildings of model 2

For 120 stories high building, 63.43° is the optimal angle and for rest of the heights, 45° is the optimum angle (Fig. 15). Although, for this kind of bracing pattern, optimum angle is again between 45° and 63.43°, variation of shear lag ratio does not follow the path of building’s stiffness (Figs. 14, 15).

Fig. 15
figure 15

Top lateral deflection versus varying angle of bracing system for buildings of model 2

Results for buildings of model 3

For this kind of bracing pattern, 63.43° is the optimal angle for the heights of 120 stories and for rest of the heights 45° is the optimum angle of diagonal bracings.

Shear lag ratio is minimum for bracing angle of 63.43° for heights of 120 and 96 stories and for the rest of the heights, 45° is the minimum angle.

For this kind of pattern, results show that for the bracing angle of 75.96° and higher, buildings stiffness is not varying in a regular path with the further increase of bracing angle. It increases once and decreases again (Figs. 16, 17).

Fig. 16
figure 16

Variation of shear lag with varying angle of bracing system for buildings of model 3

Fig. 17
figure 17

Top lateral deflection versus varying angle of bracing system for buildings of model 3

Results for buildings of model 4

For this kind of pattern, buildings of height 120, 96 and 72 stories, 63.43° bracing angle is the optimum angle and for 48 and 36 stories high buildings, 45° is the optimal angle (Figs. 18, 19).

Fig. 18
figure 18

Variation of shear lag with varying angle of bracing system for buildings of model 4

Fig. 19
figure 19

Top lateral deflection versus varying angle of bracing system for buildings of model 4

It can also be observed in the graphs of Fig. 19, that after bracing angle 63.43°, variation in stiffness of buildings follows the haphazard path.

Conclusions

Looking closely at the results of all building models together, except for building model 2, all buildings of whatever height, bracing angle between 45° and 63.43° is the critical variation which gives the least value of lateral deflection as well as of shear lag ratio. For building model 2, shear lag ratio is not minimum in this variation only.

It is found that for all building models, bracing angle of 63.43° shows the least lateral deflection for 120 stories high building and for 48 and 36 story high buildings, least top lateral deflection is coming for the bracing angle of 45° for all heights. For the heights between 120 and 48, least lateral deflection is fluctuating among the values 63.43° and 45° for all models.

Again, building models 1 and 2 have two bracing elements in a cross section of any panel, whereas models 3 and 4 are having only one bracing element in a panel. Therefore, for a material-saving design perspective, it is not possible to compare all four models together but can be done separately.

Among all models, lateral deflection of 120 stories high building with bracing angle of 63.43° is taken and compared (Fig. 20). It can be concluded with this comparison that bracing pattern of building model 1 is the best selection among models 1 and 2 and building model 4 is the best selection among models 3 and 4.

Fig. 20
figure 20

Top lateral deflection of buildings of 120 stories high with bracing angle 63.43° of all models

Among all building models, it is found that for buildings of model 1, shear lag varies the way building’s stiffness is varying. Although providing other configurations of bracing in a building are not showing any negative effect, bracing configuration of model 1 can be said as the best selection among all models.