Abstract

Most commercial and industrial facilities require very low temperatures for refrigeration and high temperatures for space heating and hot water purposes. Single stage heat pumps have not been able to meet these temperature demands and have been characterized by low capacities and coefficient of performance (COP). Cascade heat pump has been developed to overcome the weaknesses of single stage heat pumps. This study reviews recent works done by researchers on cascade heat pumps for refrigeration, heating and hot water generation. Selection of suitable refrigerants to meet the pressure and temperature demands of each stage of the cascade heat pump has been discussed. Optimization of design parameters such as intermediate temperature (low stage condensing and high stage evaporating temperatures), and temperature difference in the cascade heat exchanger for optimum performance of the cascade heat pump has been reviewed. It was found that optimising each design parameter of the cascade heat pump is necessary for maximum system performance and this may improve the exergetic efficiency, especially of cascade refrigeration systems, by about 30.88%. Cascade heat pumps have wider range of application especially for artificial snow production, in the supermarkets, for natural gas liquefaction, in drying clothes and food and as heat recovery system. The performance of cascade heat pumps can be improved by 19% when coupled with other renewable energy sources for various real time applications. Also, there is the need for much research on refrigerant charge amount of cascade heat pumps, refrigerant-refrigerant heat exchangers to be used as cascade heat exchanger, cascade heat pumps for simultaneous cooling, heating and hot water generation and on the use of variable speed compressors and their control strategies in matching system capacity especially at part load conditions.

This is a preview of subscription content, log in via an institution to check access.

Access this article

Price excludes VAT (USA)
Tax calculation will be finalised during checkout.

Instant access to the full article PDF.

Similar content being viewed by others

References

  1. Cho C, Min Choi J. Experimental investigation of a multi-function heat pump under various operating modes. Renew Energy, 2013, 54: 253–258

    Article  Google Scholar 

  2. Johnstone N, Haščič I, Popp D. Renewable energy policies and technological innovation: Evidence based on patent counts. Environ Resour Econ, 2010, 45: 133–155

    Article  Google Scholar 

  3. Aikins K A, Lee S H, Choi J M. Technology review of two-stage vapor compression heat pump system. Int J Air-Cond Ref, 2013, 21: 1330002

    Article  Google Scholar 

  4. Zubair S M, Yaqub M, Khan S H. Second-law-based thermodynamic analysis of two-stage and mechanical-subcooling refrigeration cycles. Int J Refrig, 1996, 19: 506–516

    Article  Google Scholar 

  5. Jung H W, Kang H, Yoon W J, et al. Performance comparison between a single-stage and a cascade multi-functional heat pump for both air heating and hot water supply. Int J Refrig, 2013, 36: 1431–1441

    Article  Google Scholar 

  6. Hosoz M. Performance comparison of single-stage and cascade refrigeration systems using R134a as the working fluid. Turkish J Eng Env Sci, 2005, 29: 285–296

    Google Scholar 

  7. Wang B M, Xing Z W, Wu H G. Experimental study on the performance of a twin-screw CO2 compressor in NH3/CO2 cascade refrigeration system. P I Mech Eng A-J Pow, 2010, 224: 1141–1146

    Google Scholar 

  8. Kim D H, Park H S, Kim M S. Optimal temperature between high and low stage cycles for R134a/R410A cascade heat pump based water heater system. Exp Thermal Fluid Sci, 2013, 47: 172–179

    Article  Google Scholar 

  9. Corberán J M, Martínez-Galván I, Martínez-Ballester S, et al. Influence of the source and sink temperatures on the optimal refrigerant charge of a water-to-water heat pump. Int J Refrig, 2011, 34: 881–892

    Article  Google Scholar 

  10. Jeong K, Choi J M. Capacity modulation of a cascade heat pump with the variation of compressor speed and electronic expansion valve opening. J Renew Sustain Energy, 2014, 6: 053107

    Article  Google Scholar 

  11. Di Nicola G, Giuliani G, Polonara F, et al. Blends of carbon dioxide and HFCs as working fluids for the low-temperature circuit in cascade refrigerating systems. Int J Refrig, 2005, 28: 130–140

    Article  Google Scholar 

  12. Messineo A, Panno D. Performance evaluation of cascade refrigeration systems using different refrigerants. Int J Air-Cond Ref, 2012, 20: 1250010

    Article  Google Scholar 

  13. Bhattacharyya S, Garai A, Sarkar J. Thermodynamic analysis and optimization of a novel N2O-CO2 cascade system for refrigeration and heating. Int J Refrig, 2009, 32: 1077–1084

    Article  Google Scholar 

  14. Sarkar J, Bhattacharyya S, Gopal M R. Optimization of a transcritical CO2 heat pump cycle for simultaneous cooling and heating applications. Int J Refrig, 2004, 27: 830–838

    Article  Google Scholar 

  15. Bhattacharyya S, Mukhopadhyay S, Kumar A, et al. Optimization of a CO2–C3H8 cascade system for refrigeration and heating. Int J Refrig, 2005, 28: 1284–1292

    Article  Google Scholar 

  16. Bhattacharyya S, Mukhopadhyay S, Sarkar J. CO2-C3H8 cascade refrigeration-heat pump system: Heat exchanger inventory optimization and its numerical verification. Int J Refrig, 2008, 31: 1207–1213

    Article  Google Scholar 

  17. Dubey A M, Kumar S, Agrawal G D. Thermodynamic analysis of a transcritical CO2/propylene (R744-R1270) cascade system for cooling and heating applications. Energy Conv Manage, 2014, 86: 774–783

    Article  Google Scholar 

  18. Yu P C. Refrigerant selection for sustainable future. ASHRAE J, 2007-2008: 22–26

    Google Scholar 

  19. Billiard F. Selection of refrigerants on a per-application basis: Trends. Int Inst Refrig, 2002, 1(2005): 7

    Google Scholar 

  20. Bansal P, Jain S. Cascade systems: Past, present, and future. Trans ASHRAE, 2007, 113: 245–252

    Google Scholar 

  21. Lommers C A. Air Conditioning and Refrigeration Industry Refrigerant Selection Guide-2003. 7th Ed. Melbourne Vic: Australian Institute of Refrigeration Air Conditioning and Heating Inc. (AIRAH), 2003

    Google Scholar 

  22. Xu X. Refrigerant selection in room air conditioning industry for sustainable development. Dissertation of Masteral Degree. Tokyo: The University of Tokyo, 2012

    Google Scholar 

  23. Bensafi A, Thonon B. Transcritical R744 (CO2) Heat Pumps Technician’s Manual. Villeurbanne Cedex-France: Centre Technique Des Industries Aérauliques Et Thermiques, 2007

    Google Scholar 

  24. Dopazo J A, Fernández-Seara J. Experimental evaluation of a cascade refrigeration system prototype with CO2 and NH3 for freezing process applications. Int J Refrig, 2011, 34: 257–267

    Article  Google Scholar 

  25. Sarker J, Bhattacharyya S, Lal A. Selection of suitable natural refrigerants pairs for cascade refrigeration system. P I Mech Eng A-J Pow, 2013, 227: 612–622

    Google Scholar 

  26. Ouadha A, En-Nacer M, Imine O, er al. Exergy analysis and comparision of two-stage and cascade refrigeration cycles using natural refrigerants. In: Proceedings of the Heat-SET, Heat Transfer in Components and systems for sustainable Energy Technologies Conference. Le Bourget du Lac, France, 2007

    Google Scholar 

  27. Messineo A. R744-R717 cascade refrigeration system: Performance evaluation compared with a HFC two-stage system. Energy Procedia, 2012, 14: 56–65

    Article  Google Scholar 

  28. Jadhav J S, Apte A D. Review of cascade refrigeration system with different refrigerant pairs. Int J Innov Eng Res Technol, 2015, 2: 74–81

    Google Scholar 

  29. Chae J H, Choi J M. Evaluation of the impacts of high stage refrigerant charge on cascade heat pump performance. Renew Energy, 2015, 79: 66–71

    Article  Google Scholar 

  30. Kim D H, Park H S, Kim M S. The effect of the refrigerant charge amount on single and cascade cycle heat pump systems. Int J Refrig, 2014, 40: 254–268

    Article  Google Scholar 

  31. Kim D H, Park H S, Kim M S. Characteristics of R134a/R410A cascade heat pump and optimization. In: Proceedings of the International Refrigeration and Air Conditioning Conference. West Lafayette, IN, 2012

    Google Scholar 

  32. Kilicarslan A, Hosoz M. Energy and irreversibility analysis of a cascade refrigeration system for various refrigerant couples. Energ Conv Manage, 2010, 51: 2947–2954

    Article  Google Scholar 

  33. Bingming W, Huagen W, Jianfeng L, et al. Experimental investigation on the performance of NH3/CO2 cascade refrigeration system with twin-screw compressor. Int J Refrig, 2009, 32: 1358–1365

    Article  Google Scholar 

  34. Choi J M, Kim Y C. The effects of improper refrigerant charge on the performance of a heat pump with an electronic expansion valve and capillary tube. Energy, 2002, 27: 391–404

    Article  Google Scholar 

  35. Park H, Kim D H, Kim M S. Thermodynamic analysis of optimal intermediate temperatures in R134a-R410A cascade refrigeration systems and its experimental verification. Appl Thermal Eng, 2013, 54: 319–327

    Article  Google Scholar 

  36. Ratts E B, Brown J S. A generalized analysis for cascading single fluid vapor compression refrigeration cycles using an entropy generation minimization method. Int J Refrig, 2000, 23: 353–365

    Article  Google Scholar 

  37. Agnew B, Ameli S M. A finite time analysis of a cascade refrigeration system using alternative refrigerants. Appl Thermal Eng, 2004, 24: 2557–2565

    Article  Google Scholar 

  38. Ma M, Yu J, Wang X. Performance evaluation and optimal configuration analysis of a CO2/NH3 cascade refrigeration system with falling film evaporator-condenser. Energy Conv Manage, 2014, 79: 224–231

    Article  Google Scholar 

  39. Parekh A D, Tailor P R. Thermodynamic analysis of R507A-R23 cascade refrigeration system. Int Scho Sci Res Innov, 2011, 5: 1919–1923

    Google Scholar 

  40. Fiora J J, Lima C U S, Junior V S. Theoritic-experimental evaluation of a cascade refrigeration system for low temperature applications using the pair R22/R404A. Therm Eng, 2012, 11: 7–14

    Google Scholar 

  41. Lee T S, Liu C H, Chen T W. Thermodynamic analysis of optimal condensing temperature of cascade-condenser in CO2/NH3 cascade refrigeration systems. Int J Refrig, 2006, 29: 1100–1108

    Article  Google Scholar 

  42. Lee T S, Liu C H, Chen T W. Thermodynamic analysis of optimum condensing temperature of cascade condenser for CO2/NH3 cascade refrigeration systems. In: IIR Ammonia Refrigeration Conference. Ohrid, Republic of Macedonia, 2005

    Google Scholar 

  43. Getu H M, Bansal P K. Thermodynamic analysis of an R744–R717 cascade refrigeration system. Int J Refrig, 2008, 31: 45–54

    Article  Google Scholar 

  44. Sachdeva G, Jain V, Kachhwaha S S. Performance study of cascade refrigeration system using alternative refrigerants. Int Scho Sci Res Innov, 2014, 8: 522–528

    Google Scholar 

  45. Alberto Dopazo J, Fernández-Seara J, Sieres J, et al. Theoretical analysis of a CO2-NH3 cascade refrigeration system for cooling applications at low temperatures. Appl Thermal Eng, 2009, 29: 1577–1583

    Article  Google Scholar 

  46. Kilicarslan A. An experimental investigation of a different type vapor compression cascade refrigeration system. Appl Thermal Eng, 2004, 24: 2611–2626

    Article  Google Scholar 

  47. Soltani R, Dincer I, Rosen M A. Comparative performance evaluation of cascaded air-source hydronic heat pumps. Energy Conv Manage, 2015, 89: 577–587

    Article  Google Scholar 

  48. Swanson A G, Carlson A C. Performance and energy savings of variable refrigerant technology in cold weather climates. Conservation Applied Research and Development Final Report. Minnesota Department of Commerce, Division if Energy Resources, Minnesota, USA, 2015

    Google Scholar 

  49. Jung H W, Kang H, Chung H, et al. Performance optimization of a cascade multi-functional heat pump in various operation modes. Int J Refrig, 2014, 42: 57–68

    Article  Google Scholar 

  50. Tassou S A, Qureshi T Q. Comparative performance evaluation of positive displacement compressors in variable-speed refrigeration applications. Int J Refrig, 1998, 21: 29–41

    Article  Google Scholar 

  51. Adhikari R S, Aste N, Manfren M, et al. Energy savings through variable speed compressor heat pump systems. Energy Procedia, 2012, 14: 1337–1342

    Article  Google Scholar 

  52. Ekren O, Celik S, Noble B, et al. Performance evaluation of a variable speed DC compressor. Int J Refrig, 2013, 36: 745–757

    Article  Google Scholar 

  53. Arouca L B P, Almeida A G S, Almeida F S, et al. Exergy analysis of cascade refrigeration system for low temperatures using ecological fluids. In: Proceedings of 22nd International Congress of Mechanical Engineering. Ribeirão Preto, SP, 2013. 10221–10230

    Google Scholar 

  54. Bhattacharyya S, Bose S, Sarkar J. Exergy maximization of cascade refrigeration cycles and its numerical verification for a transcritical CO2-C3H8 system. Int J Refrig, 2007, 30: 624–632

    Article  Google Scholar 

  55. Yilmaz B, Erdonmez N, Sevindir M K, Mancuhan E. Thermodynamic analysis and optimization of cascade condensing temperature of a CO2 (R744)/R404A cascade refrigeration system. In: International Refrigeration and Air Conditioning Conference. West Lafayette, IN: Herrick Laboratories, Purdue University, 2014

    Google Scholar 

  56. Mafi M, Naeynian S M M, Amidpour M. Exergy analysis of multistage cascade low temperature refrigeration systems used in olefin plants. Int J Refrig, 2009, 32: 279–294

    Article  Google Scholar 

  57. Pereira C, Lequisiga D. Technical evaluation of C3-MR and cascade cycle on natural gas liquefaction process. Int J Chem Eng Appl, 2014, 5: 451–456

    Google Scholar 

  58. Refrigeration technology for sports and leisure facilities. GEA Refrigeration Technologies. http://www.gea.com/en/binaries/Ap_Leisure_150dpi_A4Size_4C_US_tcm11-18513.pdf

  59. Sharma V, Fricke B, Bansal P. Comparative analysis of various CO2 configurations in supermarket refrigeration systems. Int J Refrig, 2014, 46: 86–99

    Article  Google Scholar 

  60. Baxter V D. IEA annex 26: Advanced supermarket refrigeration/heat recovery system. IEA Annex 26 Final Report. Canada-Denmark-Sweden-United Kingdom-United States, 2003

    Google Scholar 

  61. Sánchez D, Llopis R, Cabello R, et al. Conversion of a direct to an indirect commercial (HFC134a/CO2) cascade refrigeration system: Energy impact analysis. Int J Refrig, 2017, 73: 183–199

    Article  Google Scholar 

  62. Yoon J I, Lee H S, Oh S T, et al. Characteristics of cascade and C3MR cycle on natural gas liquefaction process. Int Scho Sci Res Innov, 2009, 59: 620–624

    Google Scholar 

  63. Hwang I S, Lee Y L. Cascade heat pump dryer performance improvement using a solar collector. ARPN J Eng Appl Sci, 2015, 10: 782–787

    Google Scholar 

  64. Kondou C, Koyama S. Thermodynamic assessment of high-temperature heat pumps using Low-GWP HFO refrigerants for heat recovery. Int J Refrig, 2015, 53: 126–141

    Article  Google Scholar 

  65. IEA Annex 35: Applications of Industrial heat pumps. IEA Heat pump programme Annex 35. Final Report. Boras, Sweden, 2014

    Google Scholar 

  66. Du K, Zhang S, Xu W, et al. A study on the cycle characteristics of an auto-cascade refrigeration system. Exp Thermal Fluid Sci, 2009, 33: 240–245

    Article  Google Scholar 

  67. Zhang J, Xu Q. Cascade refrigeration system synthesis based on exergy analysis. Comp Chem Eng, 2011, 35: 1901–1914

    Article  Google Scholar 

  68. Fernández-Seara J, Sieres J, Vázquez M. Compression-absorption cascade refrigeration system. Appl Thermal Eng, 2006, 26: 502–512

    Article  Google Scholar 

  69. Park N, Woo H S, Ha J C, et al. On the optimal water discharge temperature of air-to-water heat pump for space heating and domestic hot water. In: Proceedings of International Refrigeration and Air Conditioning Conference. West Lafayette, IN, 2010. 2497

    Google Scholar 

  70. Kaushik S C, Kumar P, Jain S. Performance evaluation of irreversible cascaded refrigeration and heat pump cycles. Energy Conv Manage, 2002, 43: 2405–2424

    Article  Google Scholar 

  71. Аndriy R. Thermodynamic analysis of cycles of the cascade heat pump plant. In: Proceedings of the Thirty-sixth Workshop on Geothermal Reservoir Engineering. Stanford, California, 2011

    Google Scholar 

  72. Rezayan O, Behbahaninia A. Thermoeconomic optimization and exergy analysis of CO2/NH3 cascade refrigeration systems. Energy, 2011, 36: 888–895

    Article  Google Scholar 

  73. Wu J, Yang Z, Wu Q, et al. Transient behavior and dynamic performance of cascade heat pump water heater with thermal storage system. Appl Energy, 2012, 91: 187–196

    Article  Google Scholar 

  74. Madani H, Claesson J, Lundqvist P. Capacity control in ground source heat pump systems part II: Comparative analysis between on/off controlled and variable capacity systems. Int J Refrig, 2011, 34: 1934–1942

    Article  Google Scholar 

Download references

Author information

Authors and Affiliations

Authors

Corresponding author

Correspondence to JongMin Choi.

Rights and permissions

Reprints and permissions

About this article

Check for updates. Verify currency and authenticity via CrossMark

Cite this article

Boahen, S., Choi, J. Research trend of cascade heat pumps. Sci. China Technol. Sci. 60, 1597–1615 (2017). https://doi.org/10.1007/s11431-016-9071-7

Download citation

  • Received:

  • Accepted:

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.1007/s11431-016-9071-7

Keywords

Navigation