Electric Arc Furnaces as a Cause of Current and Voltage Asymmetry

by
Zbigniew Olczykowski
Faculty of Transport, Electrical Engineering and Computer Science, Kazimierz Pulaski University of Technology and Humanities, 26-600 Radom, Poland
Energies 2021, 14(16), 5058; https://doi.org/10.3390/en14165058
Submission received: 13 June 2021 / Revised: 5 August 2021 / Accepted: 13 August 2021 / Published: 17 August 2021
(This article belongs to the Special Issue Voltage Unbalance Analysis in Power Distribution Networks)

Abstract

:
In the case of three-phase arc furnaces, two types of asymmetry can be distinguished: constructional and operational. The structural asymmetry is related to the construction of high-current circuits supplying the arc furnace. The knowledge of the parameters of the high-current circuit allows to determine the operating characteristics of the arc device. The author proposed a method for calculating the real values of the resistance and reactance of the high-current circuit. For this purpose, tests were made to short-circuit the electrodes with the charge. During the short-circuit, with the use of a power quality analyzer, measurements of electrical indicators were carried out, which allow to determine the parameters of the high-current circuit. A new method for determining voltage operational unbalance is also presented in this paper. The theoretical considerations presented in the article were verified in industrial conditions.

1. Introduction

Voltage and current unbalance is one of the basic problems related to the power quality, which can cause many negative effects on the power system. For many years, the main causes of asymmetry were single-phase loads, which caused a different distribution of loads in individual phases. The voltage asymmetry also caused the asymmetry of the currents consumed by the symmetrical loads, which increased further asymmetry in the power supply system. The assessment of the increase in voltage unbalance in the PCC, which is the result of the interaction of many unbalanced loads, is presented in the publication [1]. The proposed method uses the voltages and currents consumed by individual consumers recorded in real conditions. The publication [2] presents the assessment of the influence of single-phase electric consumers on voltage asymmetry.
The attention was paid to disturbances caused by non-linear devices, including the influence on the value of the current in the neutral conductor. The need to monitor electrical power quality parameters was emphasized in order to set alarms to warn of exceeding the limit values.
Currently, in power systems, there are more and more distributed energy sources, mainly photovoltaic power plants. Photovoltaic installations affect the quality of the voltage on the supply line to which they are connected. They cause, among other things, an increase in voltage and voltage asymmetry. The assessment of the power quality of PV systems supplied from distribution grids was presented in the publications [3,4,5,6]. Also [7] presents an analysis of the impact of photovoltaic systems for power quality, including a voltage imbalance. Dynamic models of the single-phase PV units are developed and utilized. Other sources of voltage asymmetry that have emerged in recent years are charging stations for electric cars [8,9,10] and energy storage [11,12].
The increasing number of devices and installations disturbing the power quality forced the application of various remedial measures. An interesting method allowing to reduce the voltage and current asymmetry is presented in [13]. The applied strategy is particularly effective in smart grids and systems using electricity storage.
The concept of dynamic programming of inverters, aimed at limiting voltage asymmetry, has been presented in publications [14,15,16], and the use of STATCOM systems is presented in publications [17,18].
Current and voltage unbalance is also caused by three-phase receivers. The asymmetry is caused by the different load of the individual phases. We encounter a similar situation in the case of arc furnaces [19]. One of the reasons for the operational asymmetry are different values of currents in individual phases supplying the furnace transformer. As a result, there is a voltage asymmetry. Through the steelworks supply networks, the voltage asymmetry is propagated to the electrical system. Voltage asymmetry also causes disturbances in the operation of the arc furnace.
The operational asymmetry is reduced by the use of the electrode position control system [20,21] and additional devices aimed at improving the energy quality [22,23,24,25]. It should also be mentioned that the arc furnaces is the source of fast voltage fluctuations [26,27,28,29,30,31]. This electromagnetic disturbance occurs with the asymmetry of currents and voltages.
The article presents issues related to current and voltage asymmetry caused by arc furnaces. The publication is a continuation of the series of articles [32,33,34] presenting the impact of electric arc furnaces on the power system.
The article presents the methods of determining voltage asymmetry and relates them to the method proposed by the author (Section 4). Based on the analysis of power quality indicators measured in the supply lines of the steelworks, the constructional and operational asymmetry caused by arc furnaces was analyzed. The method for determining the parameters of the high-current path of the electric arc furnace is presented (Section 3).
The Discussion (Section 4) presents the values of the voltage unbalance coefficients K2U determined by various methods and compared with the method proposed by the author—Table 1. Comments are presented in the Discussion and in the Conclusions.

2. Methods of Determining Voltage Asymmetry

The method of symmetrical components can be classified as one of the most known methods of determining the asymmetry coefficient [35].
In the first symmetrical system (positive or direct sequence component U1L1, U1L2, U1L3), the voltage phasors are shifted by an angle of 120° and has the same phase sequence as the asymmetrical voltage system UL1, UL2, UL3; the second symmetrical system (negative or inverse sequence component U2L1, U2L2, U2L3) has the reverse phase sequence; in the third symmetrical system (zero or homopolar sequence component U0L1, U0L2, U0L3), the voltage phasors are in phase with each other:
-
positive sequence
U _ 1 L 1 = U 1 L 1 = U 1 U _ 1 L 2 = a 2 U _ 1 L 1 U _ 1 L 3 = a U _ 1 L 1
-
negative sequence
U _ 2 L 1 = U _ 2 U _ 2 L 2 = a U _ 2 L 1 U _ 2 L 3 = a 2 U _ 2 L 1
-
zero sequence
U _ 0 L 1 = U _ 0 L 2 = U _ 0 L 3 = U _ 0
where a is the operator of rotation:
The phase voltages are the sum of the symmetrical components:
a = e j 2 3 π = 1 2 + j 3 2 a 2 = e j 4 3 π = e j 2 3 π = 1 2 j 3 2
U _ L 1 = U _ 1 L 1 + U _ 2 L 1 + U _ 0 L 1 U _ L 2 = U _ 1 L 2 + U _ 2 L 2 + U _ 0 L 2 = a 2 U _ 1 L 1 + a U _ 2 L 1 + U _ 0 L 1 U _ L 3 = U _ 1 L 3 + U _ 2 L 3 + U _ 0 L 3 = a U _ 1 L 1 + a 2 U _ 2 L 1 + U _ 0 L 1
The phase-to-phase voltages as a function of symmetrical components can be presented as the difference of the respective phase voltages:
U _ L 12 = U _ L 1 U _ L 2 = ( 1 a 2 ) U _ 1 L 1 + ( 1 a ) U _ 2 L 1 U _ L 23 = U _ L 2 U _ L 3 = ( a 2 a ) U _ 1 L 1 + ( a a 2 ) U _ 2 L 1 U _ L 31 = U _ L 3 U _ L 1 = ( a 1 ) U _ 1 L 1 + ( a 2 1 ) U _ 2 L 1
The complex factor K2U is:
K _ 2 U = U _ 2 U _ 1 = U _ L 1 + a 2 · U _ L 2 + a · U _ L 3 U _ L 1 + a · U _ L 2 + a 2 · U _ L 3 = U 2 U 1 · e j Ψ u
Ignoring the phase shift angle between the positive and negative components, we get:
| K _ 2 U | = | U _ L 1 + a 2 · U _ L 2 + a · U _ L 3 | | U _ L 1 + a · U _ L 2 + a 2 · U _ L 3 | = U 2 U 1
To assess the voltage asymmetry level, the most common is the asymmetry coefficient expressed in percent, which is the ratio the negative to the positive sequence:
K 2 U = U 2 U 1 100 %
According to the EN 61000-4-30 [36] standard, the value of the K2U asymmetry coefficient is determined by the relationship:
K 2 U = 1 3 6 · β 1 + 3 6 · β 100 %
where β:
β = U L 12 4 + U L 23 4 + U L 31 4 ( U L 12 2 + U L 23 2 + U L 31 2 ) 2
and according to the norm IEC 61000-2-12 [37] formula:
K 2 U = 6 ( U L 12 2 + U L 23 2 + U L 31 2 ) ( U L 12 + U L 23 + U L 31 ) 2 2
and by IEC 61000-2-1 [38], ANSI C84.1 [39], P29 [40] formula:
K 2 U = Δ U max U ave 100 %
where:
  • ∆Umax—maximum phase voltage deviation from the average value of three phase voltages
  • Uave—average value of three phase voltages.
In GOST 13109-97 the asymmetry coefficient K2U determined from the formulas [41]:
K 2 U = 1 12 ( [ ( 3 U L 12 4 U L 23 2 ( U L 23 2 U L 31 2 U L 12 + U L 12 ) 2 ) 2 + ( U L 23 2 U L 31 2 U L 12 ) 2 ] 1 12 ( [ ( 3 U L 12 + 4 U L 23 2 ( U L 23 2 U L 31 2 U L 12 + U L 12 ) 2 ) 2 + ( U L 23 2 U L 31 2 U L 12 ) 2 ] 100 %
where:
U 1 = 1 12 ( [ ( 3 U L 12 + 4 U L 23 2 ( U L 23 2 U L 31 2 U L 12 + U L 12 ) 2 ) 2 + ( U L 23 2 U L 31 2 U L 12 ) 2 ]
U 2 = 1 12 ( [ ( 3 U L 12 4 U L 23 2 ( U L 23 2 U L 31 2 U L 12 + U L 12 ) 2 ) 2 + ( U L 23 2 U L 31 2 U L 12 ) 2 ]
Using the Kowzan method based on nomographs, described in [42], the asymmetry coefficient is determined from the formula (17):
A C A A = U L 31 U L 12 ;   A B A A = U L 23 U L 12
then K2U is read from the nomogram.
Another method using nomographs was developed at the Institute of Energy of Ukraine [42]. The asymmetry coefficient K2U was determined according to the dependence 18.
x = U L 12 U L 31 ;   y = U L 21 U L 31
As in the previous method, K2U is read from the nomogram. Examples of nomograms are presented in the publication [42].
The article presents a new method for determining voltage asymmetry. Knowing the voltage modules UL12, UL23, UL31, the squares of the modules can be determined U L 12 2 , U L 23 2 , U L 31 2 .
U L 12 2 = U M 2 + W U 2 · cos α U 2
U L 32 2 = U M 2 + W U 2 cos ( α U 2 120 o )
U L 31 2 = U M 2 + W U 2 · cos ( α U 2 + 120 o )
For the voltages UL12, UL23, UL31, the mean value of the squares of the voltages was calculated U M 2 :
U M 2 = U L 12 2 + U L 23 2 + U L 31 2 3
W U 2 · cos α U 2 = U L 12 2 U M 2
W U 2 · sin α U 2 = 1 3 ( U L 23 2 U L 31 2 )
and a differential module W U 2 asymmetry, in the form of:
W U 2 = 2 3 ( U L 12 2 U L 23 2 ) 2 + ( U L 23 2 U L 31 2 ) 2 + ( U L 31 2 U L 12 2 ) 2
α U 2 = a r c tg U L 23 2 U L 31 2 3 ( 2 U L 12 2 U L 23 2 U L 31 2 ) + [ 1 sign ( 2 U L 12 2 U L 23 2 U L 31 2 ) ] · 90 o
To evaluate the asymmetry of the voltage squares, the difference-angle factor of the asymmetry would be used:
k _ U 2 = k U 2 e j α U 2
Then, the asymmetry differential coefficient was determined k U 2
k U 2 = W U 2 U M 2 = 2 ( U L 12 2 U L 23 2 ) 2 + ( U L 23 2 U L 31 2 ) 2 + ( U L 31 2 U L 32 2 ) 2 ( U L 12 2 + U L 23 2 + U L 31 2 )
It is found that 3 6 · β = 1 k U 2 2 . Consequently, the voltage asymmetry factor will be:
K 2 U = 1 1 k U 2 2 1 + 1 k U 2 2 = ( 1 1 k U 2 2 ) 2 ( 1 1 k U 2 2 ) ( 1 + 1 k U 2 2 ) = 1 1 k U 2 2 1 ( 1 k U 2 2 ) = 1 1 k U 2 2 k U 2 2
In the case of a small value of voltage unbalance, the K2U coefficient can be described by the Equation (29):
K 2 U 0.5 k U 2

3. Asymmetry Caused by Arc Furnaces

In the case of three-phase arc furnaces, two types of asymmetry can be distinguished: constructional and operational.

3.1. Constructional Asymmetry

As a result of different impedance values of the individual phases in the high-current path of the electric arc furnace, a constructional asymmetry arises. Knowledge of the parameters of the high-current circuit allows for the determination of the operating characteristics of the arc furnace and is necessary to determine the settings of the electrode position regulator.
Figure 1 shows the measurement system with the connection point for power quality analyzers. During the recording of electrical parameters (currents, voltages, power), the electrodes were shorted several times with the charge of the arc furnace. The method of determining the parameters of the high-current path, based on the data obtained during measurements with the use of power quality analyzers, has been patented and verified in real conditions [43].
After the electrodes are immersed in the molten metal, they are immobilized. During this time, complete short circuit of the electric arc supply system in the electric arc furnace.
Figure 2 shows the changes in active and reactive power recorded during smelting, when the electrodes were short-circuit with the charge, and Figure 3 shows a circle diagram for the furnace during the short-circuit test.
Records of currents, voltages and power (necessary to determine the reactance and resistance of the high-current circuit) were made using a 3-phase power quality analyzer-Memobox 800—Figure 1. Figure 4 shows the changes in voltage and current recorded in one of the phases on the primary side of the furnace transformer (supply line to the steel plant) during the short-circuit test.
The following part of the article presents an example of determining the impedance of a high-current circuit on the basis of measurements of power, voltage and current when the electrodes are short-circuited with the charge. The calculations, as an example, show the determination of high-current path parameters for one phase.
The impedance is calculated from the formula:
Z 1 = U L 1 I L 1
and the resistance from the formula:
R 1 = P 1 I L 1 2
The reactance can be determined from formula:
X 1 = Z 1 2 R 1 2
The transformer parameters are based on its rated data. In the calculations, they were related to the primary side, and then the final calculations were converted to the secondary side.
The transformer impedance is:
Z T = Δ U SCV · U n 2 100 · S n
resistance is as follows:
R T = Δ P Cu · U n 2 S n 2
and transformer reactance:
X T = Z T 2 R T 2
The resistance and reactance of the high-current circuit related to the upper voltage are as follows:
R hct = R 1 R T
X hct = X 1 X T
After converting to the secondary side at the kT ratio, we get the values of resistance and reactance of the high-current path (without reactance and resistance of the transformer):
R 2 hct = R hct k T 2
X 2 hct = X hct k T 2
where:
  • Sn—rated apparent power (MVA);
  • kT—ratio of the nominal voltage U1H of the upper voltage winding to the rated voltage U1L of the lower voltage winding;
  • ΔPCu—rated active power losses in transformer windings (MW);
  • ΔUscv—short-circuit voltage as a percentage of the rated voltage (%).
The further part of the article presents the calculations of the high-current path parameters for an exemplary furnace installation, the supply diagram of which is shown in Figure 1.
Calculations of the resistance and reactance of the high-current track with the furnace transformer related to the primary side of UL1 are as follows:
Z 1 = U L 1 I L 1 = 18411.7 V 145.2 A = 126.80 Ω
R 1 = P 1 I L 1 2 = 0.635 MW ( 145.2 A ) 2 = 30.11 Ω
X 1 = Z 1 2 R 1 2 = 126.8 2 26.09 2 = 123.17 Ω
The rated data of the furnace transformer are as follows:
  • Sn—rated apparent power (MVA); Sn = 10.606 MVA;
  • kT—ratio of the nominal voltage U1H of the upper voltage winding to the nominal voltage U1L of the lower voltage winding; kT = 200
  • ΔPCu—nominal active power losses in transformer windings (MW); ΔPCu = 0.179885 MW
  • ΔUscv—short-circuit voltage as a percentage of the rated voltage (%). ΔUscv = 14.91%
The transformer impedance is:
Z T = Δ U scv · U n 2 100 · S n = 14.91 · ( 30 kV ) 2 100 · 10.606 VA = 12.65 Ω
resistance is as follows:
R T = Δ P Cu · U n S n 2 = 0.179885 MW · ( 30 kV ) 2 ( 10.606 MVA ) 2 = 1.44 Ω
and transformer reactance:
X T = Z T 2 R T 2 = 12.65 2 1.44 2 = 12.57 Ω
The resistance and reactance of the high-current circuit related to the upper voltage are:
R hct = R 1 R T = 30.11 1.44 = 28.67 Ω
X hct = X 1 X T = 123.17 12.57 = 110.6 Ω
After conversion to the secondary side at the ratio kT = 200, the values of resistance and reactance of the high-current track (without reactance and resistance of the transformer) are:
R 2 hct = R hct k T 2 = 28.67 Ω 200 2 = 0.717 m Ω
X 2 hct = X hct k T 2 = 110.6 Ω 200 2 = 2.76 m Ω
For comparison, alternative calculations of the parameters of the high-current path proposed in the standard are presented [44].
The calculations of the high-current track reactance were made without taking into account the resistances, which in furnace devices do not have a significant impact on the short-circuit currents.
The short-circuit power of the network at the connection point of the furnace transformer is SSC = 500 MVA.
The parameters of the furnace transformer on the “+”, “0” and “−” taps are as follows:
  • Sn—rated apparent power: 20/20 − 15.935 − 8.314 MVA,
  • In—nominal currents:0.3849 − 0.3067 − 0.16/27.169 − 32.00 − 32.00 kA,
  • kT—nominal ratio of transformer:30 kV/425 − 287.5 − 150 V,
  • ΔUscv—short-circuit voltage as a percentage of the nominal voltage: 5.33 − 8.99 − 20.66%.
The multiplicity of the set short-circuit current of the transformer supplying the arc furnace isc is expressed by the relationship:
i sc = 100 x hct + x scv + x s
where:
  • xhct—reactance in (%) of high-current path of arc furnace,
  • xscv—transformer short-circuit reactance (equal to short-circuit voltage) in (%),
  • xs—network reactance in (%) “seen” from the transformer terminals.
The short-circuit loop reactance presented (excluding the transformer itself, for which they are set values) determine the dependencies:
x hc = I LV · X hct U LV · 100 %
where:
  • ILV—nominal phase current of the LV side of the transformer corresponding to the given tap,
  • Xhcv—high-current circuit reactance,
  • ULV—nominal voltage of the given tap on the LV side of the transformer.
HV network reactance:
x s = S n S sc · 100 %
where:
  • Sn—transformer rated apparent power at a given tap in (MVA),
  • Ssc—short-circuit apparent power of the network in (MVA).
In the case under consideration, the short-circuit current factor iscf = 1.133, corresponding to the ratio of the current measured during the transformer short-circuit test and the transformer’s rated current corresponding to a given tap, was assumed for calculations.
i scf = 201.22 A 204 A = 0.9863
x sct = u % = 15.09 %
x s = 10.606 MVA 500 MVA · 100 % = 2.12 %
i scf = 100 x hct + x sct + x s
x hct = 100 i scf · ( x sct + x s ) i scf
x hct = 100 0.9863 · ( 15.09 + 2.12 ) 0.9863 = 84.18 %
x hct = I LV · x hct U LV · 100 %
Taking account the expression in relative result the high-current circuit reactance:
X hct = x hct · U LV I LV · 100 % = 84.18 % · 110.45 V 32.0 kA · 100 % = 2.905 m Ω

3.2. Operational Asymmetry

Operational asymmetry results from the change in arc resistance caused by a different arc length during the smelting process.
Due to various changes in the parameters of the electric arc in the individual stages of the smelting, the currents flowing in the supply line of the arc furnace also change. The effect of current asymmetry is the voltage asymmetry, which may affect the correct operation of other devices.
The value of the unbalance factor K2U is largely influenced by the relationship between the short-circuit power of the supply network and the furnace transformer power. This dependence can be written by the formula:
K 2 U = K 2 I 1.1 S n S sc
where:
  • K2U—voltage asymmetry factor
  • K2I—current asymmetry factor
  • Sn—rated apparent power of arc furnace transformer
  • Ssc—short-circuit apparent power of the supply network
Based on the measurements carried out in the supply networks of the arc furnaces, it was found that the current asymmetry coefficient rarely exceeds the value of 30% [45].
Assuming according to [46,47] K2U ≤ 1% for lines with voltage above 110 kV and K2U ≤ 2% for lines up to 110 kV, it is possible to define the conditions under which unacceptable voltage asymmetry will not occur.
For lines with a voltage of 110 kV and above:
0.3 1.1 S n S SC 0.01
which corresponds to:
S n S SC 0.03
For lines with a voltage of up to 1kV:
0.3 1.1 S n S SC 0.02
which corresponds to:
S n S SC 0.06
The changes in the voltage unbalance factor K2U recorded in the weekly measurement cycle are shown in Figure 5. Measurements were made in the supply line to the steelworks (110 kV) and in the supply line for the furnace transformer (30 kV).
The short-circuit apparent power of the network in relation to the rated apparent power of the furnace transformer at the measurement points is so high that the arc furnace does not significantly affect the voltage asymmetry. The momentary increase in the voltage unbalance factor at the level of medium voltage (30 kV) is the result of disturbances caused by the arc furnace in the initial stage of smelting.
According to formula (63), the short-circuit apparent power of the supply network should be about 33 times greater than the rated apparent power of the furnace transformer, so that the voltage unbalance factor does not exceed 1%.
Figure 6 shows the changes in the currents and the asymmetry coefficient (average values measured over a measuring interval of five seconds) recorded in the steel plant supply network during one smelting.
In the initial stage of smelting, the values of the currents are the highest and differ in particular phases. Before the ignition of the electric arc, there are moments of short-circuit of individual electrodes with the charge, and these may be short-circuits of one, two or three electrodes. At this time, the asymmetry factor reaches its greatest values. Along with the melting of the charge, when the currents flow more and more steadily, the voltage asymmetry decreases.
The structural and operational asymmetry caused by the operation of the arc furnace leads to: asymmetric distribution of heating powers emitted in the electric arcs in individual phases, uneven thermal load on the internal walls of the furnace and faster wear of the electrodes in the phase in which the highest current flows. The purpose of the electric arc regulators (electrode position regulators) is to symmetrize the power dissipated in the arcs of individual phases, therefore they do not reduce the current asymmetry.
The method presented in the article, based on the data recorded during the short-circuit test of the electrodes with the charge, allows to calculate the actual parameters of the high-current circuit. Knowing the values of the high-current circuit parameters is helpful in determining the settings of the electrode adjuster.

4. Discussion

4.1. Comparison of the Asymmetry Coefficient Determined by Various Methods

The voltage asymmetry in the supply line of arc furnaces can be determined in two ways: based on the analysis of the measurement results of the asymmetry index or calculated based on known voltage values. Assessing the asymmetry on the basis of data recorded with the use of energy quality indicators seems to be the best method of assessing the K2U coefficient, because the voltage and current asymmetry value changes during the smelting process. The proposed method of determining the asymmetry factor K2U, Formulas (29) and (30), allows to determine the voltage asymmetry on the basis of known voltage values.
Table 1 shows the values of the voltage unbalance coefficients K2U determined by various methods and measured in the steel plant supply network.
The method of differential coefficients proposed by the author allows for the determination of the asymmetry coefficient with an average error, in relation to the reference values, averaging 0.87%, which is close to the error in the method presented in GOST 13109-97 [41] 0.94%.
Table 2 presents the values of the voltage asymmetry coefficients K2U proposed in [42] and determined by various methods, including the method proposed by the author.

4.2. Power Asymmetry

When using arc furnaces, the aim is to evenly distribute the power in the electric arcs of individual phases (active powers). Figure 7 shows the changes in active power registered during one melting in the arc furnace. The mean values of active powers were determined in ten seconds measuring intervals.
The correlation coefficients between the active power recorded in individual phases are as follows:
r P 1 P 2 = 0.862 ;   r P 1 P 3 = 0.890 ;   r P 2 P 3 = 0.906
Figure 8 shows correlation between the active power recorded in phase L1 and phase L2.
The electrode position controller is responsible for maintaining the symmetry of the heating power (the power generated in the electric arcs). The electrode position control system is characterized by a certain inertia. In the initial phase of melting the scrap, the electric arc is unstable. The currents in individual phases change dynamically, causing operational voltage asymmetry. The electrode position controller is not able to react quickly to changes in electric arc voltage. As a result, there are equally large changes in active power. Figure 9 shows the changes in the average, maximum and minimum power recorded during the smelting of steel in the arc furnace (for ten seconds measuring intervals).
Based on the analysis of measurement data, it can be concluded that the size of voltage unbalance is decisively influenced by the short-circuit power of the network in relation to the power of arc devices. Especially in the initial stage of the smelting, when the electric arc is initiated, rapid changes in the asymmetry coefficient were registered.

4.3. Author’s Contribution

The author’s task was to develop methods to estimate the asymmetry caused by arc furnaces:
-
Contribution to the theoretical issues related to the operation of arc furnaces is the proposed method for determining the voltage asymmetry coefficient based on differential module and differential angle—Formulas (25) and (26).
-
The calculated voltage unbalance factors K2U using the method proposed by the author were compared with the values of K2U determined by other methods, Table 1 and Table 2.
-
The proposed method for determining the parameters of the high-current circuit (structural asymmetry of the high-current circuit) based on measurements of electrical quantities in the network supplying arc furnaces has been verified in industrial conditions and has been patented.
-
The waveforms of power quality parameters presented in the article were recorded by the author during several dozen measurement cycles in the networks supplying arc furnaces. This contributes to the expansion of practical knowledge about the impact of electric arc furnaces on the power system.

5. Conclusions

The method has been patented and verified in real conditions. The operational asymmetry is limited thanks to the electrode position control system. For the efficient operation of this system, it is necessary to know the actual parameters of the high-current circuit. The method of their determination developed by the author is based on data obtained from analyzers of electric energy quality parameters when the electrodes are short-circuited with the charge. The high-current circuit reactance determined by the author, in relation to the reactance determined by the electrode supplier, differs by approx. 1%, and in relation to the one calculated according to the standard [44] by 4.12%, where the high-current circuit resistance is neglected.
In the further part of the research on the asymmetry caused by arc furnaces, the author plans to determine the effect of compensating devices on reducing the asymmetry coefficient.

Funding

This research received no external funding.

Conflicts of Interest

The author declares no conflict of interest.

References

  1. Sun, Y.; Li, P.; Li, S.; Zhang, L. Contribution determination for multiple unbalanced sources at the point of common coupling. Energies 2017, 10, 171. [Google Scholar] [CrossRef] [Green Version]
  2. Popa, G.N.; Iagăr, A.; Diniș, C.M. Considerations on current and voltage unbalance of nonlinear loads in residential and educational sectors. Energies 2021, 14, 102. [Google Scholar] [CrossRef]
  3. Al-Shetwi, A.Q.; Hannan, M.A.; Jern, K.P.; Alkahtani, A.A.; PG Abas, A.E. Power quality assessment of grid-connected PV system in compliance with the recent integration requirements. Electronics 2020, 9, 366. [Google Scholar] [CrossRef] [Green Version]
  4. Antić, T.; Capuder, T.; Bolfek, M. A Comprehensive analysis of the voltage unbalance factor in pv and ev rich non-synthetic low voltage distribution networks. Energies 2021, 14, 117. [Google Scholar] [CrossRef]
  5. Püvi, V.; Lehtonen, M. Convex Model for estimation of single-phase photovoltaic impact on existing voltage unbalance in distribution networks. Appl. Sci. 2020, 10, 8884. [Google Scholar] [CrossRef]
  6. Lin, S.; He, S.; Zhang, H.; Liu, M.; Tang, Z.; Jiang, H.; Song, Y. Robust optimal allocation of decentralized reactive power compensation in three-phase four-wire low-voltage distribution networks considering the uncertainty. Energies 2019, 12, 2479. [Google Scholar] [CrossRef] [Green Version]
  7. Islam, M.; Mithulananthan, N.; Hossain, J.; Shah, R. Dynamic voltage stability of unbalanced distribution system with high penetration of single-phase PV units. J. Eng. 2019, 2019, 4074–4080. [Google Scholar] [CrossRef]
  8. Roy, R.B.; Alahakoon, A.; Arachchillage, S.J. Grid impacts of uncoordinated fast charging of electric ferry. Batteries 2021, 7, 13. [Google Scholar] [CrossRef]
  9. Rodríguez-Pajarón, P.; Hernández, A.; Jovica, V.; Milanović, J.V. Probabilistic assessment of the impact of electric vehicles and nonlinear loads on power quality in residential networks. Int. J. Electron. Power Energy Syst. 2021, 129, 106807. [Google Scholar] [CrossRef]
  10. Nour, M.; Chaves-Ávila, J.P.; Magdy, G.; Sánchez-Miralles, A. Review of positive and negative impacts of electric vehicles charging on electric power systems. Energies 2020, 13, 4675. [Google Scholar] [CrossRef]
  11. Held, L.; Mueller, F.; Steinle, S.; Barakat, M.; Suriyah, M.R.; Leibfried, T. An optimal power flow algorithm for the simulation of energy storage systems in unbalanced three-phase distribution grids. Energies 2021, 14, 1623. [Google Scholar] [CrossRef]
  12. Bozalakov, D.; Mnati, M.J.; Laveyne, J.; Desmet, J.; Vandevelde, L. Battery storage integration in voltage unbalance and overvoltage mitigation control strategies and its impact on the power quality. Energies 2019, 12, 1501. [Google Scholar] [CrossRef] [Green Version]
  13. Dumnic, B.; Popadic, B.; Milicevic, D.; Vukajlovic, N.; Delimar, M. Control strategy for a grid connected converter in active unbalanced distribution systems. Energies 2019, 12, 1362. [Google Scholar] [CrossRef] [Green Version]
  14. Nejabatkhah, F.; Li, Y.W.; Tian, H. Power quality control of smart hybrid AC/DC microgrids: An overview. IEEE Access 2019, 7, 52295–52318. [Google Scholar] [CrossRef]
  15. Yu, Y.; Wang, Z.; Wan, X. Optimal current balance control of three-level inverter under grid voltage unbalance: An adaptive dynamic programming approach. Energies 2019, 12, 2864. [Google Scholar] [CrossRef] [Green Version]
  16. Shigenobu, R.; Nakadomari, A.; Hong, Y.Y.; Mandal, P.; Takahashi, H.; Senjyu, T. Optimization of voltage unbalance compensation by smart inverter. Energies 2020, 13, 4623. [Google Scholar] [CrossRef]
  17. Moradian, M.; Soltani, J.; Arab-Markadeh, G.R.; Shahinzadeh, H.; Amirat, Y. A new grid-connected constant frequency three-phase induction generator system under unbalanced-voltage conditions. Electronics 2021, 10, 938. [Google Scholar] [CrossRef]
  18. Jin, Y.; Wang, J.; Liu, Y.; Sai, X.; Ji, Y. Analysis of unbalanced clustered voltage and control strategy of clustered voltage balancing for cascaded H-bridge STATCOM. J. Mod. Power Syst. Clean Energy 2019, 7, 1697–1708. [Google Scholar] [CrossRef] [Green Version]
  19. Samet, H.; Golshan, M.E.H. A wide nonlinear analysis of reactive power time series related to electric arc furnaces. Electr. Power Energy Syst. 2012, 36, 127–134. [Google Scholar] [CrossRef]
  20. Yakimov, I.A.; Maklakov, A.S.; Voronin, S.S.; Maklakova, E.A. Results of modeling operation of the high-speed regulator of non-contact secondary voltage of furnace transformer of the high-power arc steel furnace. Procedia Eng. 2017, 206, 1853–1860. [Google Scholar] [CrossRef]
  21. Lozynskyi, O.Y.; Lozynskyi, A.O.; Paranchuk, Y.S.; Paranchuk, R.Y. Synthesis and analysis of arc furnace electrical mode control system on the basis of three-dimensional phase currents vector distribution. Electr. Eng. Electromech. 2019, 4, 26–34. [Google Scholar] [CrossRef]
  22. Ali, F.; Arbab, M.N.; Ahmad, G.; Ashraf, M.; Sarim, M. An SVC controller for power quality improvement of a heavily loaded grid. Mehran Univ. Res. J. Eng. Technol. 2020, 39, 247–256. [Google Scholar] [CrossRef]
  23. Jebaraj, B.S.; Bennet, J.; Kannadasan, R.; Alsharif, M.H.; Kim, M.K.; Aly, A.A.; Ahmed, A.H. Power quality enhancement in electric arc furnace using matrix converter and static var compensator. Electronics 2021, 10, 1125. [Google Scholar] [CrossRef]
  24. Torabian Esfahani, M.; Vahidi, B. Electric arc furnace power quality improvement by applying a new digital and predicted-based TSC control. Turk. J. Electr. Eng. Comput. Sci. 2016, 24, 3724–3740. [Google Scholar] [CrossRef]
  25. Lange, A.G.; Redlarski, G. Selection of C-type filters for reactive power compensation and filtration of higher harmonics injected into the transmission system by arc furnaces. Energies 2020, 13, 2330. [Google Scholar] [CrossRef]
  26. Cernan, M.; Müller, Z.; Josef Tlusty, J.; Valouch, V. An improved SVC control for electric arc furnace voltage flicker mitigation. Int. J. Electr. Power Energy Syst. 2021, 129, 106831. [Google Scholar] [CrossRef]
  27. Akkaya, S.; Salor, O. Enhanced spectral decomposition method for light flicker evaluation of incandescent lamps caused by electric arc furnaces. J. Fac. Eng. Archit. Gazi Univ. 2019, 34, 987–1005. [Google Scholar]
  28. Kiyoumarsi, A.; Ataei, M.; Hooshmand, R.; Kolagar, A.D. Electric arc furnace voltage flicker mitigation by applying a predictive method with closed loop control of the TCR/FC compensator. J. Electr. Eng. Technol. 2010, 5, 116–128. [Google Scholar] [CrossRef] [Green Version]
  29. García-Cerrada, A.; García-González, P.; Collantes, R.; Gómez, T.; Anzola, J. Comparison of thyristor-controlled reactors and voltage-source inverters for compensation of flicker caused by arc furnaces. IEEE Trans. Power Deliv. 2000, 15, 1223–1231. [Google Scholar] [CrossRef] [Green Version]
  30. Sarma, P.M.; Jayaram Kumar, S.V. Electric arc furnace flicker mitigation in a steel plant using a statcom. Int. J. Eng. Sci. Innov. Technol. 2013, 2, 227–231. [Google Scholar]
  31. Singh, A.; Singh, R.K.; Singh, A.K. Power Quality Issues of Electric Arc Furnace and their Mitigations—A Review. Int. J. Adv. Eng. Res. Sci. 2017, 4, 237114. [Google Scholar] [CrossRef]
  32. Łukasik, Z.; Olczykowski, Z. Estimating the impact of arc furnaces on the quality of power in supply systems. Energies 2020, 13, 1462. [Google Scholar] [CrossRef] [Green Version]
  33. Olczykowski, Z. Modeling of voltage fluctuations generated by arc furnaces. Appl. Sci. 2021, 11, 3056. [Google Scholar] [CrossRef]
  34. Łukasik, Z.; Olczykowski, Z. Evaluation of flicker of light generated by arc furnaces. Energies 2021, 14, 3901. [Google Scholar]
  35. Fortescue, C.L. Method of symmetrical coordi-nates applied to the solution of polyphase net-works. Trans. AIEE 1918, 37, 1027–1140. [Google Scholar]
  36. EN 61000-4-30:2015-05 (EMC)—Part 4-30: Testing and Measurement Techniques—Power Quality Measurement Methods. Available online: https://webstore.iec.ch/preview/info_iec61000-4-30%7Bed3.0.RLV%7Den.pdf (accessed on 15 August 2021).
  37. IEC 61000-2-12:2003: Compatibility Levels for Low-Frequency Conducted Disturbances and Signalling in Public Medium-Voltage Power Supply Systems. Available online: https://webstore.iec.ch/publication/4130 (accessed on 15 August 2021).
  38. IEC 61000-2-1:1990: Description of the Environment—Electromagnetic Environment for Low-Frequency Conducted Disturbances and Signalling in Public Power Supply Systems. Available online: https://webstore.iec.ch/publication/4127 (accessed on 15 August 2021).
  39. ANSI C84.1: American National Standard for Electric Power Systems and Equipment. Available online: https://www.nema.org/Standards/Pages/American-National-Standard-for-Electric-Power-Systems-and-Equipment-Voltage-Ratings.aspx (accessed on 15 August 2021).
  40. Engineering Recommendation P29: Planning Limits for Voltage Unbalance in the Unitet Kingdom, The Electricity Council. 1990. Available online: https://www.nienetworks.co.uk/documents/security-planning/er-p29.aspx (accessed on 15 August 2021).
  41. GOST 13109–13197: Electric Energy. Electromagnetic Compatibility of Technical Equipment. Power Quality Limits in the Public Power Supply Systems. Available online: http://docs.cntd.ru/document/1200104301 (accessed on 15 August 2021).
  42. Kowalski, Z. Unbalance in Power Systems (Asymetria w układach elektroenergetycznych); PWN (Polish Scientific Publishers): Warszawa, Poland, 1987. (In Polish) [Google Scholar]
  43. Olczykowski, Z.; Czyż, J. The Method of Determining the Electrical Parameters, Especially the Resistance and Reactance of the High-Current Path of the Arc Furnace (Sposób wyznaczania parametrów elektrycznych zwłaszcza rezystancji i reaktancji toru wielkoprądowego pieca łukowego). Patent No. 224767, 5 July 2016. (In Polish). [Google Scholar]
  44. International Electrotechnical Commission (IEC). Test Methods for Direct Arc Furnaces; IEC standard, Publication 676; Central Office of IEC: Geneve, Switzerland, 1980. [Google Scholar]
  45. Rak, J. Influence of AC ARC Furnace on Parameters of Industrial Medium-Voltage Network. In Proceedings of the 5th International Conference Electrical Power Quality and Utilization, Cracow, Poland, 15–17 September 1999. [Google Scholar]
  46. Ordinance of the Minister of Economy of May 4, 2007 on the Detailed Conditions for the Functioning of the System (Rozporządzenie Ministra Gospodarki z dnia 4 maja 2007 r. w sprawie szczegółowych warunków funkcjonowania systemu). Available online: http://prawo.sejm.gov.pl/isap.nsf/DocDetails.xsp?id=WDU20070930623 (accessed on 15 August 2021). (In Polish)
  47. PN-EN 50160:2014. Parameters of the Supply Voltage in the Public Power Networks; Polish Committee of Standardization; Polish Committee of Standardization: Warsaw, Poland, 2014; 2010p, Available online: https://sklep.pkn.pl/pn-en-50160-2010p.html (accessed on 15 August 2021).
Figure 1. Place of measurement of electrical parameters.
Figure 1. Place of measurement of electrical parameters.
Energies 14 05058 g001
Figure 2. Changes in active and reactive power during smelting when the electrodes were short-circuited with the charge.
Figure 2. Changes in active and reactive power during smelting when the electrodes were short-circuited with the charge.
Energies 14 05058 g002
Figure 3. Circle diagram of an arc furnace for the short-circuit condition of the electrodes to the charge.
Figure 3. Circle diagram of an arc furnace for the short-circuit condition of the electrodes to the charge.
Energies 14 05058 g003
Figure 4. Voltage and current changes during the test of short-circuit of the electrodes with the charge.
Figure 4. Voltage and current changes during the test of short-circuit of the electrodes with the charge.
Energies 14 05058 g004
Figure 5. Changes in the asymmetry coefficient recorded during the weekly measurement cycle in the supply lines of the steel plant (110 kV) and the furnace transformer (30 kV).
Figure 5. Changes in the asymmetry coefficient recorded during the weekly measurement cycle in the supply lines of the steel plant (110 kV) and the furnace transformer (30 kV).
Energies 14 05058 g005
Figure 6. Changes in the currents in individual phases and the asymmetry coefficient recorded in the steel plant supply network during one smelting.
Figure 6. Changes in the currents in individual phases and the asymmetry coefficient recorded in the steel plant supply network during one smelting.
Energies 14 05058 g006
Figure 7. Changes in active power recorded during one melting in the arc furnace.
Figure 7. Changes in active power recorded during one melting in the arc furnace.
Energies 14 05058 g007
Figure 8. Correlation between the active power recorded in phase L1 and phase L2.
Figure 8. Correlation between the active power recorded in phase L1 and phase L2.
Energies 14 05058 g008
Figure 9. Changes in active power recorded in phase L1 during one melting in the arc furnace.
Figure 9. Changes in active power recorded in phase L1 during one melting in the arc furnace.
Energies 14 05058 g009
Table 1. Values of the asymmetry coefficient calculated by various methods developed from [32].
Table 1. Values of the asymmetry coefficient calculated by various methods developed from [32].
Measured Voltages Expressed in Nominal Voltage (%)K2U
MeasurementIEC 61000-2-12IEC 61000-4-30IEC 61000-2-1 ANSI C84.1GOST 13109-97Nomogram INomogram IIAuthor
105.85; 103.31; 104.681.451.4021.4011.2471.35191.411.421.369
103.15; 101.41; 102.770.951.0291.0261.0060.9881.011.021.023
103.94; 101.73; 102.971.341.2411.2391.1711.1981.311.311.231
101.47; 101.36; 101.960.40.3570.3570.3510.3810.360.360.356
Table 2. Values of the asymmetry coefficient calculated by various methods and developed from data from [42].
Table 2. Values of the asymmetry coefficient calculated by various methods and developed from data from [42].
Voltages (%) According to Data from [42]K2U
CalculationIEC 61000-2-12IEC 61000-4-30IEC 61000-2-1 ANSI C84.1GOST 13109-97Nomogram INomogram IIAuthor
94.54; 103.18; 89.558.68.3188.4277.538.4378.628.618.343
102.67; 109.33; 96.007.67.4987.5216.4917.5227.557.517.456
Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations.

Share and Cite

MDPI and ACS Style

Olczykowski, Z. Electric Arc Furnaces as a Cause of Current and Voltage Asymmetry. Energies 2021, 14, 5058. https://doi.org/10.3390/en14165058

AMA Style

Olczykowski Z. Electric Arc Furnaces as a Cause of Current and Voltage Asymmetry. Energies. 2021; 14(16):5058. https://doi.org/10.3390/en14165058

Chicago/Turabian Style

Olczykowski, Zbigniew. 2021. "Electric Arc Furnaces as a Cause of Current and Voltage Asymmetry" Energies 14, no. 16: 5058. https://doi.org/10.3390/en14165058

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop