Thermal comfort evaluation in an educational building with air conditioning located in the warm tropical climate of Colombia

and

Published under licence by IOP Publishing Ltd
, , Citation M Balbis-Morejon and A Noya-Sambrano 2020 IOP Conf. Ser.: Mater. Sci. Eng. 844 012030 DOI 10.1088/1757-899X/844/1/012030

1757-899X/844/1/012030

Abstract

The objective of this work is to evaluate the perception of thermal comfort that students have in building 10 of the Universidad de la Costa located in the city of Barranquilla. For the investigation the methods for the thermal comfort evaluation are analyzed, selecting the Steady-State methodology of Fanger according to the ASHRAE 55 Standard. With the application of the surveys, the thermal sensation that the students had in the building was evaluated, which was preferably fresh and thermal acceptability where 87% responded satisfactorily to indoor climate conditions in classrooms. It was also obtained that the perception of inner thermal comfort is between 21.1 ° C and 23 ° C of temperature. With the results obtained, recommendations are issued to ensure that students feel thermal comfort and the proper regulation of air conditioning systems.