1 Introduction

The energy obtained from alternative energy sources is transferred to power grids through inverters. In high-power applications, three-phase inverters are used, and in low-power applications, single-phase inverters are used [1, 2]. Voltage-source inverters are widely used in grid-connected systems owing to their simplicity and reliability. Three-phase voltage source inverters can be implemented as three-wire, four-wire, and four-leg systems [3,4,5,6].

Grid-connected inverters are expected to have high power quality, high efficiency, and high reliability in renewable energy applications. Therefore, inverter topology and control techniques play important roles in grid-connected systems.

Voltage-source inverters are connected to the grid via filters. Different filters can be selected between inverters and grids, such as L, LC, and LCL filter. The L filter allows the use of a simple current-control strategy in the inverter. There is only one control loop, and grid current is used as a feedback signal. However, the inverter must operate at a relatively high switching frequency, or a high-value L filter must be used to meet the harmonic standards such as IEEE 929-2000 and IEEE 519. Because a high switching frequency causes high switching losses, L filters are not utilized in high-power renewable applications. To increase the harmonic attenuation of the L filter, an LC filter is used with an isolation transformer, but it is not generally used in grid-connected inverters, unlike stand-alone inverters. The lowest total harmonic distortion (THD) value is obtained with LCL filters at the same frequency compared with other filters. However, the LCL filter design is quite complicated owing to resonance and reactive power problems. It is important to determine filter component values in order to prevent resonance and to decrease reactive power generated by capacitors [7,8,9]. Additional passive damping techniques and complex control algorithms are used to suppress resonance. In the passive damping technique, additional resistance, capacitance, and/or inductance are required [10, 11]. Current and voltages of the capacitor and inductances are used in the control algorithm. Thus, an additional two or more control loops make the control algorithm more difficult [12].

In medium and large power-inverter applications, neutral point clamped (NPC) inverters are preferred because of their low voltage stress and low switching losses. NPC inverters have three voltage levels, i.e., −Vdc/2, 0, and Vdc/2, and thus, the voltage drop on switching devices is reduced. Therefore, switching losses decrease. However, the control algorithm becomes more complex and conduction losses increase because of a series connection of two switches on the upper and lower arms in NPC inverters [13, 14].

Grid synchronization is important for grid-connected inverters. The synchronization algorithm determines the grid angle that is used for rotating reference-frame (dq) conversion. Reference voltages and currents are produced using the angle to meet the power-quality standards. Different synchronization algorithms are used in the literature. The atan algorithm is a simple method for detecting the grid angle. It is realized in two different frames, dq and αβ. The reference frame components are filtered, and the αβ components of the grid voltage are used in an atan trigonometric function to calculate the angle. The disadvantages of the method are its poor performance in the case of fluctuating frequency and unbalanced grid voltage [15]. In recent years, the widely used synchronization technique, which has synchronous rotating frame phase-locked loops (SRF-PLLs), has been utilized. It has good performance when the grid voltage is balanced and not polluted by harmonics. Such disturbances affect the SRF-PLL dynamic-response performance [16]. Different filtering techniques are used to enhance the performance of SRF-PLL under distorted and unbalanced grid-voltage conditions [17, 18].

In this study, a new highly efficient three-phase grid-connected parallel inverter system is proposed. The proposed system is developed for grid-connected systems owing to the importance of efficiency in renewable energy systems. The proposed system includes two inverters. The main inverter operates at low switching frequency and transfers active power to the grid, while the auxiliary inverter compensates for the grid-current ripple. Thus, no active power is processed by the auxiliary inverter, and the current is lower compared with the main inverter. Although the auxiliary inverter acts as an active filter, the control algorithm of the inverter is easier than that of the active filters. In active filters, the reference current is calculated from the grid current using different methods [19,20,21], whereas this is more easily accomplished in the proposed system. In addition, the main purpose of utilizing the auxiliary inverter that is different from the active filter is an increased system efficiency compared to a single six-switch three-phase inverter with an L filter.

The proposed system is modelled in MATLAB and analyzed in terms of the DC-link voltage, switching frequency, and filter inductance values for a 10-kW output power. The characteristic curves of the system are given, and depending on these curves, the optimum system parameters are selected to provide a THD value of less than 5% of the grid current. The control of the system is quite simple because of the use of a basic L filter.

A prototype has been realized for a 10-kW output power. The main inverter and auxiliary inverter are controlled via the dSPACE real-time controller and analogue controller, respectively.

2 System description

The proposed three-phase voltage-source grid-connected parallel inverter system is shown in Fig. 1. The system includes two voltage-source inverters. To obtain the required THD results, a single inverter should operate at relatively high switching frequencies, and in this case, the efficiency is lower owing to high switching losses. In the proposed system, the main inverter operates at a low switching frequency to obtain lower switching losses. Hence, the ripple in the main inverter current is large, and the THD value of the current is high.

Fig. 1
figure 1

Proposed grid-connected parallel inverter system

The auxiliary inverter processes only reactive power to compensate the distortion in the main inverter current. The auxiliary inverter is controlled via the hysteresis current control (HCC). The operating frequency varies owing to HCC, but it is always higher than that of the main inverter. The power processed by the auxiliary inverter is low. Hence, the losses on the auxiliary inverter are very low. The DC-link voltage of the auxiliary inverter is obtained from the grid via the current control.

The L filters are connected between the inverters and the grid. Although the L filter has less harmonic attenuation than the LC and LCL filters, it is preferred because of design and control simplicity.

3 Modelling of proposed system

The proposed system is modelled with the assumptions that the DC-link voltage is constant, the switching devices are ideal, and grid voltages are balanced.

In a three-phase symmetrical system without a neutral line,

$$v_{sa} + v_{sb} + v_{sc} = 0$$
(1)
$$i_{a} + i_{b} + i_{c} = 0$$
(2)

where vsa, vsb, vsc and ia, ib, ic define grid phase voltages and currents, respectively.

Applying the Kirchhoff’s current law for each phase, three-phase circuit equations for each inverter are obtained as given in (3) and (4). The parameters k, v1, L1, R1, and i1 define the phase name {a, b, c}, phase voltage, inductance, inductor-equivalent series resistance, and phase current of the main inverter, respectively.

$$v_{1k} = L_{1} \frac{{{\text{d}}i_{1k} }}{{{\text{d}}t}} + R_{1} i_{1k} + v_{sk} + v_{n0}$$
(3)
$$v_{n0} = \frac{\text{1}}{\text{3}}(v_{{\text{1}}a} + v_{{\text{1}}b} + v_{{\text{1}}c} )$$
(4)

Inverter phase voltages change with each leg-switching state. This can be defined as

$$v_{{{\text{1}}k}} = S_{{\text{1}}k} V_{dc{\text{1}}} = \left\{ {\begin{array}{*{20}l} {V_{dc{\text{1}}} } \hfill & {S_{{\text{1}}k} = \text{1}} \hfill \\ 0\hfill & {S_{{\text{1}}k} = 0} \hfill \\ \end{array} } \right.$$
(5)

where Vdc1 defines the DC-link voltage of the main inverter. The leg-switching state is defined by S1. In the main inverter, if the upper switch is ON, then S1 = 1, and if the lower switch is ON, then S1 = 0.

By combining (3), (4), and (5), the mathematical model of the main inverter can be defined in a three-phase (abc) reference frame as:

$$S_{ 1k} V_{dc 1} = v_{sk} + R_{ 1} i_{ 1k} + L_{ 1} \frac{\text{d}}{{{\text{d}}t}}(i_{ 1k} ) + \frac{{S_{ 1a} + S_{ 1b} + S_{ 1c} }}{ 3}V_{dc 1}$$
(6)

Because the middle point of the DC-link is connected to the grid neutral in the auxiliary inverter, it can be modelled as three single-phase grid-connected inverters, as shown in (7)–(9):

$$v_{2k} = L_{2} \frac{{{\text{d}}i_{2k} }}{{{\text{d}}t}} + R_{2} i_{2k} + v_{sk}$$
(7)
$$v_{ 2k} = S_{ 2k} \frac{{V_{dc 2} }}{ 2} = \left\{ {\begin{array}{*{20}l} {\frac{{V_{dc 2} }}{ 2}} \hfill & {S_{ 2k} = 1} \hfill \\ {\frac{{ - V_{dc 2} }}{ 2}} \hfill & {S_{ 2k} = { - 1}} \hfill \\ \end{array} } \right.$$
(8)
$$S_{ 2k} \frac{{V_{dc 2} }}{ 2} = v_{sk} + R_{ 2} i_{ 2k} + L_{ 2} \frac{\text{d}}{{{\text{d}}t}}(i_{ 2k} )$$
(9)

The parameters v2, L2, R2, and i2 define the auxiliary inverter phase voltage, auxiliary inverter inductor, auxiliary inverter inductor-equivalent series resistance, and auxiliary inverter phase current, respectively. S becomes 1 and -1 in the auxiliary inverter, unlike the main inverter.

The sum of the parallel inverter currents produces the grid current:

$$i_{k} = i_{ 1k} + i_{ 2k}$$
(10)

The state-space model of the grid-connected parallel inverters can be written using (6):

$$\left\{\begin{aligned} &\frac{{\text{d}}{\varvec{x}}}{{\text{d}}t} = \varvec{Ax} + \varvec{Bu} \\ &\varvec{y} = \varvec{Cx} \\ \end{aligned}\right.$$
(11)

where the state and input vectors are defined as:

$$\varvec{x} = \left[ {\begin{array}{*{20}c} {i_{1a} } & {i_{1b} } & {i_{1c} } & {i_{2a} } & {i_{2b} } & {i_{2c} } \\ \end{array} } \right]^{\text{T}}$$
(12)
$$\varvec{u} = \left[ {\begin{array}{*{20}c} {S_{1a} V_{dc1} - v_{sa} - (\frac{{S_{1a} + S_{1b} + S_{1c} }}{3})V_{dc1} } \\ {S_{1b} V_{dc1} - v_{sb} - (\frac{{S_{1a} + S_{1b} + S_{1c} }}{3})V_{dc1} } \\ {S_{1c} V_{dc1} - v_{sc} - (\frac{{S_{1a} + S_{1b} + S_{1c} }}{3})V_{dc1} } \\ {S_{2a} \frac{{V_{dc2} }}{2} - v_{sa} } \\ {S_{2b} \frac{{V_{dc2} }}{2} - v_{sb} } \\ {S_{2c} \frac{{V_{dc2} }}{2} - v_{sc} } \\ \end{array} } \right]$$
(13)

The state and input coefficient matrices are

$$\left\{ {\begin{array}{*{20}l} {\varvec{A} = \left[ {\begin{array}{*{20}c} { - \frac{{R_{1} }}{{L_{1} }}{\varvec{I}}_{3\times3} } & {{\mathbf{0}}_{3\times3} } \\ {{\mathbf{0}}_{3\times3} } & { - \frac{{R_{2} }}{{L_{2} }}{\varvec{I}}_{3\times3} } \\ \end{array} } \right]\,} \hfill \\ {\varvec{B} = \left[ {\begin{array}{*{20}c} {\frac{1}{{L_{1} }}{\varvec{I}}_{3\times3} } & {{\mathbf{0}}_{3\times3} } \\ {{\mathbf{0}}_{3\times3} } & {\frac{1}{{L_{2} }}{\varvec{I}}_{3\times3} } \\ \end{array} } \right]} \hfill \\ \end{array} } \right.$$
(14)

The output matrix C is a unit matrix with a dimension of 6 × 6. The output variables are phase currents of parallel inverters, and the grid current defined in (10) can be calculated by adding the parallel inverter currents, as shown in Fig. 2.

Fig. 2
figure 2

Total current at the output of state-space equation

4 Control of proposed system

The main function of the grid-connected inverter is to control the magnitude and phase angle of the grid current. The real power is controlled via the current magnitude, and active power is adjusted via the phase angle. In the proposed system, two parallel inverters are connected to the grid with an L filter, as shown in Fig. 3. Each inverter is controlled with a different control technique. In the main inverter, the output current is controlled using space-vector pulse-width modulation (SVPWM). This control technique is more appropriate for a three-wire three-phase inverter. The advantages of this technique are the constant switching frequency, low harmonic content, well-defined spectrum, optimum switching signals, and high DC-link voltage utilization. The optimum switching pattern provides a low switching number and low switching losses. The SVPWM technique is widely used in three-phase grid-connected inverters [22].

Fig. 3
figure 3

Block diagram of three-phase grid-connected voltage-source parallel inverters and system control algorithm

Because an auxiliary inverter eliminates the current ripple in the grid current, it requires a fast response. The HCC technique meets the requirements of the auxiliary inverter control. The nonlinear control technique, HCC, simultaneously realizes the current error compensation and PWM generation. It has an inherent peak-current protection, fast dynamic response, robustness against the parameter variation, and simplicity. Although the control algorithm is easy to implement, the sampling frequency should be high in the control system. Its performance depends on the hysteresis bandwidth, and the bandwidth affects the switching frequency [23, 24]. The control algorithm of the system is shown in Fig. 3.

The main inverter reference current is the reference grid current. The grid current should be in phase with the grid voltage for the maximum active-power transfer. The three-phase grid voltages are measured, and they are used to determine the grid angle (θ). Theta is determined via the SRF-PLL algorithm. The three-phase voltages are transformed to the dq reference frame via the transformation matrix (16) in the phase detector. The q-component output of the grid voltage (vq) from the phase detector is used to detect grid angle. The error of vq is passed through the PI controller and added to the nominal frequency (ωn) of the grid voltage. The reference value of v * q is set to zero. The resultant signal is the grid frequency. The grid angle is determined by integrating the grid frequency, and is used to transform the three-phase voltage to the dq reference frame at the beginning of the algorithm. The block diagram of the SRF-PLL algorithm is given in Fig. 4. Using θ and the reference power, the reference currents in the dq coordinate system are calculated. The measured three-phase currents are transformed to the dq coordinate system and compared with the measured dq currents. By summing the output of the PI controllers (Kp = 1.5, KI = 0.001), the coupling components, and grid voltage, the inverter reference voltages in the dq coordinate system are obtained, and these reference components are converted into αβ components. The voltage-reference components in αβ reference voltages are used in the SVPWM generation. Switching signals are generated using voltage references, the grid angle, and DC-link voltage.

Fig. 4
figure 4

SRF-PLL algorithm grid synchronization

The main inverter current follows the reference grid current with an error owing to the high current ripple. This error causes a high THD value in the grid current. The auxiliary inverter is utilized to eliminate the current error and to decrease the THD value. To eliminate the current error, it is required to control the auxiliary inverter very rapidly. Therefore, the HCC technique is preferred to control the auxiliary inverter. The reference current of the auxiliary inverter is the main inverter current error.

$$i_{2j}^{*} = i_{1j}^{*} - i_{1j} \quad {j = a, b, c}$$
(15)
$$\varvec{T} = \frac{2}{3}\left[ {\begin{array}{*{20}l} {\cos (\omega t)} \hfill & {\cos (\omega t - \frac{{2\uppi}}{3})} \hfill & {\cos (\omega t + \frac{{2\uppi}}{3})} \hfill \\ { - \sin (\omega t)} \hfill & { - \sin (\omega t - \frac{{2\uppi}}{3})} \hfill & { - \sin (\omega t + \frac{{2\uppi}}{3})} \hfill \\ \end{array} } \right]$$
(16)

Because the DC-link consists of two capacitors connected in series, the voltages of capacitors should be regulated. The regulation is realized with a phase-a current. In the positive cycle of the grid voltage, the upper capacitor voltage is regulated. The average voltage of the upper capacitor and the error between the reference and actual value is calculated at the beginning of the positive half-cycle. The error is regulated with a PI controller (Kp = 0.02, KI = 5e−6). The same algorithm is applied to the lower capacitor in the negative half-cycle of the grid voltage. The outputs of the PI controllers are added to the auxiliary inverter phase-a current reference.

5 Power loss calculation of inverters

The energy loss of a semiconductor switch is the sum of the conduction losses (ECOND) and switching losses (ESW).

$$E_{TOTAL} = E_{COND} + E_{SW}$$
(17)

The conduction losses of the insulated-gate bipolar transistor (IGBT) and diode are calculated from (18) and (19), as given in [25, 26].

$$E_{IGBT,COND} = \int\limits_{0}^{\pi } {v_{CEsat} (t)i_{C} (t){\text{d}}t}$$
(18)
$$E_{DIODE,COND} = \int\limits_{0}^{\pi } {v_{f} (t)i_{f} (t){\text{d}}t}$$
(19)

where vCEsat is the collector-emitter saturation voltage of IGBT, iC is the collector current of the IGBT, vf is the forward voltage drop of the diode, and if is the diode forward current. vCEsat is obtained from the iC-vCEsat curve, and vf is obtained from the if-vf curve from the datasheet.

The switching-energy loss is the sum of turn-on (Eon) and turn-off (Eoff) losses in the switching devices, as given by

$$E_{SW} = E_{SW,on} + E_{SW,off}$$
(20)

The switching losses of the IGBT and diode are calculated depending on the voltage and current values from the Eon and Eoff curves that are given in the datasheet. The current values are used in (18)–(20), and conduction energy losses are calculated. The power-loss calculation process is shown in Fig. 5.

Fig. 5
figure 5

Block diagram of power-loss calculation

6 Design procedure

The characteristic curves of the system are given in Figs. 6, 7, 8 and 9. These curves depend on various DC-link voltages, filter inductances, hysteresis bandwidth values (ΔI), and switching frequencies (fsw1), and are obtained using MATLAB for a 220 V grid voltage, 50-Hz grid frequency, and 10 kW output power. The parameters are determined to obtain low THD and low switching frequency in the auxiliary inverter. The characteristic curves of the main inverter and 5% THD limiting surface are shown in Figs. 6 and 7. From Fig. 6, it is seen that the THD1 decreases when fsw1 increases. The operation below the THD limiting surface can be ensured using different inductance and frequency values. For fsw1 = 9 kHz, the THD variation is shown according to the DC-link voltage Vdc1 and filter inductance L1 in Fig. 7. It is seen that the THD increases with increased DC-link voltage. In contrast, the increase of the L1 filter inductor results in a decrease in the THD value.

Fig. 6
figure 6

Main inverter current THD for different values of L1 and fsw1

Fig. 7
figure 7

Main inverter current THD for different values of Vdc and L1 for fsw1 = 9 kHz

Fig. 8
figure 8

Grid-current THD for different values of ΔI and L2

Fig. 9
figure 9

Auxiliary inverter average switching frequency for different values of ΔI and L2

If the energy is transferred to the grid using only the main inverter, L1 and/or fsw1 must be high enough to provide the required THD value. The proper parameters for this case can be selected from the curves. In the proposed parallel-inverter system, the goal is to decrease the switching losses of the main inverter regardless of the grid-current THD value. The auxiliary inverter is utilized to compensate the grid current harmonics in order to meet harmonic standards. The main inverter-current error becomes the auxiliary inverter reference current. Therefore, the selection of L1 and fsw1 is important to determine the performance of the auxiliary inverter because it determines the current of the auxiliary inverter.

To compensate for the dead-time, inductor, and switch conduction voltage drops, and to control stability, a 700 V DC voltage was selected. The main inverter filter inductor was selected as L1 = 3 mH. If the main inverter is operated as a standalone, the switching frequency should be selected to be approximately 9 kHz to meet the 5% THD limit. In the proposed method, the switching frequency of the main inverter is selected as fsw1 = 3 kHz in order to decrease switching losses, and the ripple of the grid current is eliminated via an auxiliary inverter.

In the auxiliary inverter, the IGBTs are switched at high voltage. Thus, the switching frequency is an important limitation. The auxiliary inverter currents are low, but the current rise rate is high. Therefore, the selection of the auxiliary inverter inductance L2 and HCC bandwidth ΔI is important. L2 and ΔI values that provide a 5% THD limit and achievable fsw2 are selected from the characteristic curves as L2 = 2 mH, and ΔI = 0.7 A. fsw2 is not constant, and varies during the grid period. The average value of fsw2 is approximately 20 kHz.

The control performance depends on the bandwidth value of HCC. The increase in the bandwidth value degrades the control performance, and the THD value of the grid current increases, as shown in Fig. 8. A narrowing of the hysteresis bandwidth decreases the THD, but increases the switching frequency fsw2, as shown in Figs. 8 and 9.

7 Simulation results

The proposed system was simulated in MATLAB/Simulink. The simulation parameters were determined from characteristic curves in Figs. 6, 7, 8 and 9. The three-phase current waveforms of the main inverter operating standalone at fsw1 = 3 kHz are shown in Fig. 10. In this case, THD is 14% and does not meet the standards. The auxiliary inverter current that compensates the main inverter current is shown in Fig. 11.

Fig. 10
figure 10

Three-phase currents of the main inverter

Fig. 11
figure 11

Phase-a current of the auxiliary inverter

Three-phase grid currents produced by two parallel inverters are given in Fig. 12. The total grid current has a 4.33% THD that meets the standards. The auxiliary inverter average switching frequency is approximately 20 kHz. Even though the average switching frequency appears to be high, the switching losses are negligible owing to the low level of the auxiliary inverter current.

Fig. 12
figure 12

Three-phase grid currents of parallel inverter

Figure 13 shows simulation results of grid synchronization for three fundamental periods. Three-phase grid voltages and the grid angle, which is determined through PLL, are given in Fig. 13a and b, respectively. As seen in Fig. 13b, the grid angle changes over 0–2π (rad). The angle is 4π/3 (rad) when the phase-a voltage is zero, phase-b voltage is negative, and phase-c voltage is positive. The angle reaches 2π rad when the phase-a voltage becomes a maximum and other phase voltages are equal. The angle varies in 2π (rad) for 20 ms, which is the fundamental period of the grid voltage.

Fig. 13
figure 13

Grid synchronization

Figure 14 shows the DC-link capacitor voltages of the auxiliary inverter. The DC-link consists of two series-connected capacitors, and the middle point is connected to the grid neutral. Therefore, the voltages of the capacitors should be regulated. The regulation can be seen in Fig. 14. Each capacitor voltage varies between 348 V and 352 V. The total voltage ripple of 4 V is observed in each capacitor voltage. The upper and lower capacitor voltages move in opposite directions. The upper capacitor voltage rises, while the lower capacitor voltage decreases for 10 ms.

Fig. 14
figure 14

Auxiliary inverter DC-link voltage

Figure 15 shows the three-phase grid currents for the standalone operation of the main inverter at fsw = 9 kHz. A similar THD value is obtained using the proposed method, as shown in Fig. 13. In this case, the main inverter operates at a 3 kHz switching frequency, and switching losses are thus decreased by a factor of three times.

Fig. 15
figure 15

Three-phase grid currents of the main inverter at fsw = 9 kHz

To evaluate the efficiency improvement of the proposed parallel inverter system, the efficiency of parallel inverters is calculated with Vdc = 700 V, L1 = 3 mH, L2 = 2 mH, fsw1 = 3 kHz, and ΔI = 0.7 A, and the efficiency of the standalone inverter is calculated with Vdc = 700 V, L1 = 3 mH, and fsw1 = 9 kHz. Figure 16 illustrates the efficiency curves of the proposed system and the standalone operation of the main inverter for different output power levels. The filter inductor losses are not taken into consideration. The standalone inverter efficiency is 97.6%, and the parallel-inverter system efficiency is 98.6% for the rated power. The efficiency is increased by 1% with the proposed control of the parallel inverters.

Fig. 16
figure 16

Efficiency curves for the standalone inverter fsw = 9 kHz and proposed inverter system

8 Experimental study

A laboratory prototype of the proposed system is realized for a 10 kW output power. The control algorithm of the main inverter was developed in MATLAB/Simulink and implemented using dSPACE. The efficiency and THD measurements were acquired using a HIOKI 3390 energy analyzer.

The main inverter is supplied using a 700 V DC source, and the auxiliary inverter regulates its DC voltage through the grid with an active rectifier operation. The hysteresis control of the auxiliary inverter is implemented using analogue circuitry.

The system parameters and components used in the prototype are given in Table 1. The three-phase current waveforms of the main inverter operating standalone at fsw1 = 9 kHz are shown in Fig. 17. The measured THD and efficiency values for this operation are 4.46% and 97.45%, respectively.

Table 1 Summary of the proposed system
Fig. 17
figure 17

Grid currents of the standalone inverter at fsw = 9 kHz

To decrease the switching losses, the main inverter switching frequency is decreased to 3 kHz. The three-phase currents of this operation are shown in Fig. 18. As can be clearly seen from the figure, the low switching frequency causes a high current ripple. The measured THD and efficiency of this operation are 14.7% and 98.36%, respectively.

Fig. 18
figure 18

Three-phase currents of the main inverter for fsw = 3 kHz

To lower the THD of the grid current, an auxiliary inverter is operated. In Fig. 19, the main inverter current (Ch4), auxiliary inverter current (Ch3), and grid current (Ch2) are shown with respect to the related phase voltage (Ch1). Although there is a high current ripple in the main inverter current, this ripple is eliminated in the grid current by the auxiliary inverter. Three-phase grid currents are shown in Fig. 20.

Fig. 19
figure 19

Proposed system operation with respect to phase voltage

Fig. 20
figure 20

Three-phase grid currents of the proposed system

Voltage waveforms of the DC-link capacitors in the auxiliary inverter are shown in Fig. 21. The voltages are measured from the output of the voltage sensors. In the experimental setup, two LEM LV25-P voltage sensors are used to measure each capacitor voltage. It has a 2500:1000 conversion ratio. The resistors used in the measurement board are 47 kΩ and 330 Ω. Thus, the ratio of the actual and measured voltage is 57.14. The actual capacitor voltage of 350 V is measured at approximately 6.1 V, as seen in Fig. 21.

Fig. 21
figure 21

DC-link capacitor voltages of the auxiliary inverter

The measured THD and efficiency values are 4.33% and 97.86% in the proposed system, respectively. Experimental results taken from the proposed system are given in Table 2.

Table 2 Experimental results of the proposed system

The measured efficiencies given in Table 2 are slightly different from the simulation study results shown in Fig. 15. This difference is caused by the filter inductor losses. The inductors are modelled as ideal elements in the simulation. However, in the experimental study, it is seen that inductor losses affect the overall system efficiency.

The software Melcosim was used to estimate intelligent power module (IPM) losses of the main inverter. For a 9 kHz operating frequency, the IPM losses of the main inverter are calculated as 240 W, and for a 3 kHz operation, the IPM losses are calculated as 126 W. According to the Melcosim software results, the losses of the proposed system are as given in Table 3.

Table 3 Losses of the proposed system

It can be seen that filter inductor losses are an important factor that determines the efficiency of grid-connected inverter systems. The losses due to the filter inductor depends on many factors. From the experimental results, it is observed that the main filter inductor losses are increased when the main inverter is operated at lower frequency.

9 Conclusion

In this paper, a new three-phase grid-connected converter system was proposed. The proposed system includes two inverters. The main inverter operates at a low switching frequency and transfers all of the active energy from a DC source to the grid. The low-power auxiliary inverter operates at a high frequency to compensate for the grid-current ripple. The goal is to produce a grid current with a low THD value and to obtain a higher efficiency.

The proposed system was modelled in MATLAB and analyzed in terms of the DC-link voltage, switching frequency, and filter-inductance values for a 10-kW output power. The characteristic curves of the system are given, and depending on these curves, the optimum system parameters are selected to provide a THD value of less than 5% of the grid current. Owing to the operation at low switching frequencies, the main inverter switching losses decrease compared with a single inverter for the same THD value that is obtained from parallel inverters. According to the experimental results, the proposed system efficiency and grid current THD value are measured as 97.86% and 4.33%, respectively, whereas for a single two-level inverter, the values are 97.46% and 4.46%, respectively. The proposed system provides a 0.4% efficiency improvement for a 10-kW grid-connected system. A higher efficiency value can be obtained using a more efficient filter inductor design and using different solid-state switching devices.